Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
211 Sequencing
Interval
XX Seconds
Seconds
View
Modify
NA
5
0
60
•The sequence interval for the multi-phase display and status LEDs on the control HMI.
The LEDs will alternately display the status of each connected device for the specified
interval.
212 Multi-Phase
DeltaCalc Mode
Off
---
View
Modify
NA
Off
NA
NA
•Enables the DeltaCalc feature on a multi-phase control.
•The settings options are: Off; Basic; Advanced.
•See
Section 6: Control Features: DeltaCalc feature
for more information on this parameter.
220 Auto Tap Dead
Phase mode
Disabled
View
Modify
NA
Disabled
NA
NA
•This setting will enable Tap-Dead-Phase functionality for a multi-phase control. Using
this function, the control will use power from powered phases to operate the tap changer
of dead phases.
•The settings options include: Disabled, Tap To Neutral, Ganged Mode.
221 Tap Dead
Phase
Inactive
View
NA
NA
NA
NA
NA
•This will display the operational status of the Auto Tap Dead Phase mode function, either
Inactive or Active.
222 Delay Timer
15 Seconds
Seconds
View
Modify
NA
15
1
180
•When a condition occurs that would enable the Auto Tap Dead Phase mode, the activation of
the function will be delayed for this period of time.
260 Com 1
Tx Messages
XXXXX
---
View
NA
Operate
Reset* to
0
NA
NA
•Count of Transmitted Messages from Com 1.
261 Com 1
Rx Messages
XXXXX
---
View
NA
Operate
Reset* to
0
NA
NA
•Count of Received Messages from Com 1.
262 Com 1
Rx Errors
XXXXX
---
View
NA
Operate Reset* to 0
NA
NA
•Count of Receive Errors from Com 1.
263 Com 2
Tx Messages
XXXXX
---
View
NA
Operate Reset* to 0
NA
NA
•Count of Transmitted Messages from Com 2.
264 Com 2
Rx Messages
XXXXX
---
View
NA
Operate Reset* to 0
NA
NA
•Count of Received Messages from Com 2.
82
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control