Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
815 2179 Ignore
Master Address
Disabled
---
View
Modify
NA
Enabled
NA
NA
•This is the Com 1 setting that allows the device to accept commands and requests from
masters other than that listed in the Master Device Address field.
•The available options are: Disabled; Enabled.
815 2179 Device
Address
XXXX
---
View
Modify
NA
1
0
2047
•This is the Com 1 setting that specifies the address, from 0 to 2047, of the RTU instance
on the control.
815 2179 Select
Timeout
XXXXXXX mSec
MilliSec
View
Modify
NA
5000
0
3600000
•This is the Com 1 setting that determines the amount of time that can elapse between a
"select" and "operate" command for systems that employ select-before-operate commands.
815 2179 User Map
Selection
CL-7 Default Event
---
View
Modify
NA
CL-7
Default
NA
NA
•The selection of the active 2179 protocol map for Com 1. The available options are: User
1; User 2; CL-7 Default; CL-7 Default Events; CL-7 Advanced; CL-6 Default; CL-6 Default
Events; CL-7 3Ph Default; CL-7 3Ph Default Evt; CL-7 3Ph Advanced.
815 2179 Dead Sync
Timeout
10 Msec
Msec
View
Admin
NA
10
1
1000
•A period of time during which the received data line is idle, defining the end of the
previous message. This idle time is the dead-line sync period. The control is now
synchronized so that the next byte received is considered the beginning of a new message.
This parameter is for Com 1.
815 2179 Master Time
Format
Local
NA
View
Modify
NA
Local
NA
NA
•This selects the master time format for use with the 2179 protocol. This parameter is for
Com 1.
•Options include: Local; UTC.
816 Modbus Device
Address
XXX
---
View
Modify
NA
1
1
247
•This is the Com 1 setting that specifies the address, from 1 to 247, of the RTU instance
on the control.
•Configuration parameters for Modbus are displayed when protocol is available.
816 Modbus User Map
Selection
CL-7 Default
---
View
Modify
NA
CL-7
Default
NA
NA
•The selection of the active Modbus protocol map for Com 1. The available options are:
User 1; User 2; CL-7 Default; CL-7 Default Events; CL-7 Advanced; CL-6 Default; CL-6
Default Events; CL-7 3Ph Default; CL-7 3Ph Default Evt; CL-7 3Ph Advanced.
816 Modbus Listening
Port Number
XXXXX
---
View
Modify
NA
502
1
65534
•This defines the IP port number that will be monitored for incoming MODBUS TCP
connections.