Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
477 Remote #2 Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote latch #2 Voltage Reduction Value for Alternate Configuration 1.
478 Remote #3 Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote latch #3 Voltage Reduction Value for Alternate Configuration 1.
479 # of Pulse
Reduction Steps
XX
---
View
Modify
NA
0
0
10
•The Remote Pulse Voltage Reduction number of steps for Alternate Configuration 1.
480 % of Voltage Red
Per Pulse Step
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote Pulse Voltage Reduction % per step for Alternate Configuration 1.
481 Present Voltage
Reduction Step
XX
---
View
NA
NA
NA
NA
NA
•The Remote Pulse Voltage Reduction Present Voltage Reduction Step for Alternate
Configuration 1.
482 SOFT-ADD-AMP
Limits
Off
---
View
Modify
NA
Off
NA
NA
•The SOFT-ADD-AMP Limits feature enabled for Alternate Configuration 1.
483 SOFT-ADD-AMP
High Limit
XX
---
View
Modify
NA
16
NA
NA
•The SOFT-ADD-AMP High Limit for Alternate Configuration 1.
484 SOFT-ADD-AMP
Low Limit
XX
---
View
Modify
NA
-16
NA
NA
•The SOFT-ADD-AMP Low Limit for Alternate Configuration 1.
485 Voltage Limiter
Mode
Off
---
View
Modify
NA
Off
NA
NA
•Voltage Limiter Mode enabled for Alternate Configuration 1.
486 High Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
130.0
120.0
135.0
•The Voltage Limiter High Limit for Alternate Configuration 1.
487 Low Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
105.0
105.0
120.0
•The Voltage Limiter Low Limit for Alternate Configuration 1.
488 Voltage Limiter
Fast Resp. Delay
XX Seconds
Seconds
View
Modify
NA
3
1
60
•The Voltage Limiter Fast Resp. Delay for Alternate Configuration 1.
88
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control