Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
508 Rev Line Drop
Comp. Resistance
XX.X Volts
Volts
View
Modify
NA
0.0
-96.0
96.0
•Reverse Line Drop Compensation Resistance for Alternate Configuration 2.
509 Rev Line Drop
Comp. Reactance
XX.X Volts
Volts
View
Modify
NA
0.0
-96.0
96.0
•Reverse Line Drop Compensation Reactance for Alternate Configuration 2.
510 Control
Operating Mode
Sequential
---
View
Modify
NA
Sequential
NA
NA
•The Control Operating Mode for Alternate Configuration 2.
511 Reverse Sensing
Mode
Locked Forward
---
View
Modify
NA
Locked
Forward
NA
NA
•The Reverse Sensing Mode for Alternate Configuration 2.
512 Reverse Current
Sense Threshold
X %
%
View
Modify
NA
1
1
5
•The Reverse Current Sense Threshold for Alternate Configuration 2.
513 Auto Operation
Blocking Status
Normal
---
View
Modify
NA
Normal
NA
NA
•The Auto Operation Blocking Status for Alternate Configuration 2.
514 Voltage
Reduction Mode
Off
---
View
Modify
NA
Off
NA
NA
•The Voltage Reduction Mode for Alternate Configuration 2.
515 Local/Digital
Reduction Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Local/Digital Reduction Value for Alternate Configuration 2.
516 Remote #1 Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote latch #1 Voltage Reduction Value for Alternate Configuration 2.
517 Remote #2 Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote latch #2 Voltage Reduction Value for Alternate Configuration 2.
518 Remote #3 Value
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote latch #3 Voltage Reduction Value for Alternate Configuration 2.
519 # of Pulse
Reduction Steps
XX
---
View
Modify
NA
0
0
10
•The Remote Pulse Voltage Reduction number of steps for Alternate Configuration 2.
520 % of Voltage Red
Per Pulse Step
XX.X %
%
View
Modify
NA
0.0
0.0
10.0
•The Remote Pulse Voltage Reduction % per step for Alternate Configuration 2.
90
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control