Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
031 Rev Compensated
Voltage High
XXX.X Volts
MM-DD-YYYY HH:MM:SS
Volts
View
NA
Operate
Reset*
NA
NA
•This is the highest value of the calculated secondary voltage at the center of regulation
during reverse power flow since last reset, as a demand value, according to the demand
time interval at FC 46.
•The reverse line-drop compensation settings for resistance and reactance (FC 54 and FC 55)
are used in calculating this value.
•Date and time of the occurrence of the highest compensated voltage is displayed.
•The control requires source voltage from a differential or source potential transformer or
from the source voltage calculation (see FC 39) to obtain this parameter. Lack of this
voltage will result in the parameter displaying dashes.
031 Rev Compensated
Voltage Low
XXX.X Volts
MM-DD-YYYY HH:MM:SS
Volts
View
NA
Operate
Reset*
NA
NA
•This is the lowest value of the calculated secondary voltage at the load center during
reverse power flow since last reset, as a demand value, according to the demand time
interval at FC 46.
•The reverse line-drop compensation settings for resistance and reactance (FC 54 and FC 55)
are used in calculating this value.
•Date and time of the occurrence of the lowest compensated voltage is displayed.
•The control requires source voltage from a differential or source potential transformer or
from the source voltage calculation (see FC 39) to obtain this parameter. Lack of this
voltage will result in the parameter displaying dashes.
031 Rev Compensated
Voltage Present
XXX.X Volts
Volts
View
NA
NA
NA
NA
NA
•This is the present value of the calculated secondary voltage at the load center during
reverse power flow, as a demand value, according to the demand time interval at FC 46.
•The reverse line-drop compensation settings for resistance and reactance (FC 54 and FC 55)
are used in calculating this value.
•The control requires source voltage from a differential or source potential transformer or
from the source voltage calculation (see FC 39) to obtain this parameter. Lack of this
voltage will result in the parameter displaying dashes.
032 Reverse Load
Current High
XXX.X Amps
MM-DD-YYYY HH:MM:SS
Amps
View
NA
Operate
Reset*
NA
NA
•This is the highest value of the load current during reverse power flow since the last
reset, as a demand value, according to the demand time interval at FC 46.
•Date and time of the occurrence of the highest load current is displayed.
•The control requires source voltage from a differential or source potential transformer or
from the source voltage calculation (see FC 39) to obtain this parameter. Lack of this
voltage will result in the parameter displaying dashes.
56
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control