![background image](http://html.mh-extra.com/html/eaton/cooper-power-series/cooper-power-series_installation-operation-and-maintenance-manual_524277110.webp)
Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
801 Serial Tx
Disable Delay
XXXX mSec
MilliSec
View
Modify
NA
5
0
3000
•For Com 1, when the control is set for transmit control handshaking, a delay may be
required between the time when the data transmission is terminated and the transmit enable
signal is disabled.
•See Figure 19.
Serial
Tx
Enabled
Delay
Transmit
Disabled
Transmit
Enabled
Data
Message
Serial
Tx
Disabled
Delay
Figure 19. Data transmission from the CL-7 control to the communication system
for handshaking applications
801 Serial Echo Mode
Disabled
---
View
Modify
NA
Disabled
NA
NA
•When serial communications is active, this parameter will enable or disable the echo mode
for Com 1.
•Options include: Disabled; Enabled
802 IP Address
XXX.XXX.XXX.XXX
---
View
Modify
NA
NA
NA
NA
•The Com 1 IP Address setting.
802 Subnet Mask
XXX.XXX.XXX.XXX
---
View
Modify
NA
NA
NA
NA
•The Com 1 Subnet Mask setting.
802 Gateway
XXX.XXX.XXX.XXX
---
View
Modify
NA
NA
NA
NA
•The Com 1 Gateway setting.
802 MAC Address
XX:XX:XX:XX:XX:XX
---
View
NA
NA
NA
NA
NA
•The Com 1 MAC Address setting.
803 TCP IP Socket
Re-Int.
Disabled
---
View
Admin
NA
Disabled
NA
NA
•This enables a feature that will reinitiate the TCP/IP communications socket periodically.
803 TCP IP Socket
Re-Int Timeout
24 Hours
Hours
View
Admin
NA
24
1
336
•This sets the period between TCP/IP socket resets.
104
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control