Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
574 SOFT-ADD-AMP
Low Limit
XX
---
View
Modify
NA
-16
NA
NA
•The SOFT-ADD-AMP Low Limit for Alternate Configuration 3.
575 Voltage Limiter
Mode
Off
---
View
Modify
NA
Off
NA
NA
•Voltage Limiter Mode enabled for Alternate Configuration 3.
576 High Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
130.0
120.0
135.0
•The Voltage Limiter High Limit for Alternate Configuration 3.
577 Low Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
105.0
105.0
120.0
•The Voltage Limiter Low Limit for Alternate Configuration 3.
578 Voltage Limiter
Fast Resp. Delay
XX Seconds
Seconds
View
Modify
NA
3
1
60
•The Voltage Limiter Fast Resp. Delay for Alternate Configuration 3.
579 Voltage Limiter
Delay
XX Seconds
Seconds
View
Modify
NA
10
1
60
•The Voltage Limiter Delay for Alternate Configuration 3.
580 Time Between
Taps
XX Seconds
Seconds
View
Modify
NA
0
0
10
•The Voltage Limiter Time Between Taps for Alternate Configuration 3.
581 Tap To Neutral
Off
---
View
Modify
NA
Off
NA
NA
•The Tap to Neutral setting for Alternate Configuration 3.
582 Bias Co-Gen Alt
Mode
Locked Reverse
---
View
Modify
NA
Locked
Reverse
NA
NA
•The Bias Co-generation Alt Mode setting for Alternate Configuration 3. See FC 58.
600 Voltage Sag
Monitoring
Off
View
Modify
NA
Off
NA
NA
• This will turn on or turn off the voltage sag monitor feature on the control.
• The settings options include: On; Off
601 Level1 Threshold
70.0 %
%
View
Modify
NA
70.0
50.0
70.0
•The level 1 voltage sag set point given as a percentage Demand Metering value of Forward
Load Voltage Present or Reverse Load Voltage Present as applicable.
•A voltage sag below this level for the duration of the value of the Level 1 Threshold
Timer Value (FC 603) will cause the control to record a Level 1 sag event.
94
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control