Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
830 Protocol / Port
Type
Serial DNP
---
View
Modify
NA
Serial DNP
NA
NA
•Protocol and Port setting for Com 2. Not all options are resident on the control, some
will require additional hardware to enable. The available protocol options will display
according to port type.
•Possible options for a particular configuration include: Disabled; DNP / Serial; DNP /
Ethernet; IEC 101 / Serial; IEC 104 / Ethernet; 2179 / Serial; Modbus / Serial; Modbus /
Ethernet.
830 LoopShare
Communications
Disabled
---
View
Modify
NA
Disabled
NA
NA
•This will enable or disable LoopShare Communications for Com 2. The options include:
Disabled; Enabled.
830 ProView NXG
Session
Disabled
---
View
Modify
NA
Disabled
NA
NA
•This will enable or disable sessions with ProView NXG for Com 2. The options include:
Disabled; Enabled.
830 ProView NXG
Address
XXXXX
---
View
Modify
NA
65519
0
65519
•The Com 2 address for communications with ProView NXG is set here.
831 Serial Baud Rate
9600 BPS
---
View
Modify
NA
9600 BPS
NA
NA
•This is the Com 2 Serial Communications Baud Rate setting. The options available are: 300
BPS; 600 BPS; 1200 BPS; 2400 BPS; 4800 BPS; 9600 BPS; 19200 BPS; 38400 BPS; 57600 BPS;
115200 BPS.
831 Serial Parity
None
---
View
Modify
NA
None
NA
NA
•This sets for Com 2 the data parity parameter to be used on the serial communications
channel.
•The available options are: None; Odd; Even.
831 Serial CTS
Support
Disabled
---
View
Modify
NA
Disabled
NA
NA
•This setting determines for Com 2 if CTS/RTS handshaking will be used to control the
serial communications channel.
•The available options are: Disabled; Enabled.
831 Serial Tx
Enable Delay
XXXX mSec
MilliSec
View
Modify
NA
5
0
3000
•For Com 2, when the control is set for transmit control handshaking, the user may require
a delay between the time when the transmission is enabled to when data is transmitted.
•Example: If the transmit enable were used as a keying device for a transmitter or modem,
a “warm-up” period may be necessary before data can be transmitted.
•See Figure 20.