Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
048 Current
Calibration
XXX.X mAmps
MilliAmp
View
Admin
NA
See Note
100.0
400.0
•The current which the control actually measures in mA, is displayed at FC 48.
•The control is designed for 200 mA as the rated CT secondary output current and will
meter to 800 mA with no loss of accuracy.
•To calibrate, this value is compared to a reference ammeter and, if different, is changed
to display the correct value.
•Note: A default calibration factor is programmed into non-volatile memory at the factory;
adjustments should not be necessary.
•See
Section 8: Troubleshooting: Control calibration
•In addition to the low and high limits, the user must enter a value that is within 5% of
the displayed value.
049 Tap Changer Type
Cooper QD8
---
View
Modify
NA
“-----”
(Invalid)
NA
NA
•This function code identifies the tap-changer type. Changing this function code changes
the control’s sampling rate to accommodate varying tap-changer types.
•Options include: Eaton's Cooper Power series QD8; Eaton's Cooper Power series QD5; Eaton's
Cooper Power series QD3; Eaton's Cooper Power series Spring Drive; Eaton's Cooper Power
series Direct Drive; Siemens; General Electric; Howard; LTC Reinhausen; ITB, Toshiba, User
Defined.
050 System Calendar
and Clock
MM-DD-YYYY HH:MM:SS
---
View
Modify
NA
See Note
NA
NA
•Editing is always in the format MM-DD-YYYY and with the 24 Hour clock.
•Note: The default is Jan. 1, 1970.
•Refer to
Section 6: Control Features: Calendar/clock
050 UTC Time Zone
GMT-05:00
---
View
NA
NA
NA
NA
NA
•Used to set the time zone with respect to Greenwich Mean Time. The options include: GMT-
12:00 to GMT-01:00; Greenwich Mean Time; GMT+01:00 to GMT+13:00.
•This cannot be edited via the keypad; use of ProView NXG interface software is required
for editing.
051 Reverse
Set Voltage
XXX.X Volts
Volts
View
Modify
NA
120.0
100.0
135.0
•The set voltage is the voltage level to which the control will regulate on the 120 V or
240 V base during reverse power flow.
Section 6: Control Features: Reverse power operation
.
•If an alternate configuration is active, the fourth LCD line displays which one is active,
e.g. (ALT CONFIG 1).
•If FC 148 Nominal Load Voltage is set to 240 Volts, limits are expanded (doubled).
•If FC 148 is set to System Line Voltage, this setting must be set in terms of the system
line voltage. For example, on a 7200 V system, with a desired set voltage 1% above the
nominal voltage, the setting would be 7272.
63
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control