Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
020 Forward Load
Voltage Present
XXX.X Volts
Volts
View
NA
NA
NA
NA
NA
•This is the present reading of secondary output voltage of the regulator, as a demand
value, according to the demand time interval at FC 46
021 Fwd Compensated
Voltage High
XXX.X Volts
MM-DD-YYYY HH:MM:SS
Volts
View
NA
Operate
Reset*
NA
NA
•This is the highest value of the calculated secondary voltage at the center of regulation
since the last reset, as a demand value, according to the demand time interval at FC 46.
•The forward line-drop compensation settings for resistance and reactance (FC 4 and FC 5)
are used in calculating this value.
•Date and time of the occurrence of the highest compensated voltage is displayed.
021 Fwd Compensated
Voltage Low
XXX.X Volts
MM-DD-YYYY HH:MM:SS
Volts
View
NA
Operate
Reset*
NA
NA
•This is the lowest value of the calculated secondary voltage at the center of regulation
since the last reset, as a demand value, according to the demand time interval at FC 46.
•The forward line-drop compensation settings for resistance and reactance (FC 4 and FC 5)
are used in calculating this value.
•Date and time of the occurrence of the lowest compensated voltage is displayed.
021 Fwd Compensated
Voltage Present
XXX.X Volts
Volts
View
NA
NA
NA
NA
NA
•This is the present value of the calculated secondary output voltage of the load center,
as a demand value, according to the demand time interval at FC 46.
•The forward line-drop compensation settings for resistance and reactance (FC 4 and FC 5)
are used in calculating this value.
022 Forward Load
Current High
XXX.X Amps
MM-DD-YYYY HH:MM:SS
Amps
View
NA
Operate
Reset*
NA
NA
•This is the highest value of the load current since last reset, as a demand value,
according to the demand time interval at FC 46.
•Date and time of the occurrence of the highest load current is displayed.
022 Forward Load
Current Low
XXX.X Amps
MM-DD-YYYY HH:MM:SS
Amps
View
NA
Operate
Reset*
NA
NA
•This is the lowest value of the load current since last reset, as a demand value,
according to the demand time interval at FC 46.
•Date and time of the occurrence of the lowest load current is displayed.
022 Forward Load
Current Present
XXX.X Amps
Amps
View
NA
NA
NA
NA
NA
•This is the present reading of the load current as a demand value, according to the
demand time interval at FC 46.
52
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018
CL-7 Voltage Regulator Control