Default Configuration Settings
GSC400’s are factory programmed and shipped with default settings loaded into the controller.
Table 17 – GSC400 Default Settings
FUNCTION
DEFAULT SETTINGS
J1939
Manufacturer
John Deere
Display Group 1
Disable
Display Group 2
Disable
DTC Display
Disable
Active DTC Log
Disable
Read Stored DTC
Disable
Auto Power ECM
Disable
ECM Power Delay
6 seconds
Cummins Idle
Disable
Conversion Method
Conversion 2
High Engine Temp
Input Pin
Input Pin 2
Signal Source
Switch
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Fahrenheit
Warning Level
200°F
Failure Level
220°F
Oil Pressure
Input Pin
Disable
Signal Source
Switch
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
PSI
Warning Level
20 PSI
Failure Level
15 PSI
Fuel Level
Input Pin
Disabled
Signal Source
Switch
Bypass Delay
30 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
25%
Failure Level
5%
Oil Level
Input Pin
Disable
Signal Source
Switch
Bypass Delay
10 Seconds
Switch Setting
SW Closed = Fail