Table 6 – Event Log Entries
An “*” beside the Event Entry indicates the Event is a GSC400 event. All other
events are failures (see page section 5.11 on page 38).
Event Entry
Description
ADC SWITCH FAILURE
ADE READ FAILURE
ADE WRITE FAIL
These are internal GSC400 failures. Try power cycle
the GSC400. If the failure occurs repeatedly the unit
could be defected.
AUTO ENABLE*
Auto button on front face of controller pressed.
GSC400 placed in AUTO mode.
AUXILIARY FAIL
The Auxiliary Fail digital input was active. See
Table
15
on page 67.
CHARGE OVER*
The battery charge run period for low battery is
finished and the generator has shut down. See section
6.9.1 on page 69.
CHARGE START*
The generator has started up due to low battery
voltage. See section 6.9.1 on page 69.
Config Fail 1
Config Fail 2
The Config Fail 1/2 digital input has been triggered.
See
Table 15
on page 67. The text displayed is the
text the user entered from the PC Interface.
EEPROM FAILURE
This is an internal GSC400 failure. Try to power
cycle the GSC400. If the failure occurs repeatedly the
unit could be defected.
EMERGENCY STOP
The emergency stop input (located on the digital input
terminal) has been activated.
EPS LOADS ERROR
AC current sensing indicating that the generator is
outputting current when the generator is not running.
This could indicate something is wrong with the
GSC400. See section 5.11.2 on page 39.
EXERCISER DELAYED
TO NEXT RUN*
If the generator was running when it was due for an
exercise run. See section 6.7 on page 66
EXERCISER OVER*
The exerciser run period is over and the generator has
shut down. See section 6.7 on page 66.
EXERCISER START*
The generator has started up to exercise itself. See
section 6.7 on page 66.
HIGH BATTERY
Failure occurred due to high battery voltage. See
section 6.9 on page 69.
HIGH ENGINE TEMP
Failure occurred due to high engine coolant
temperature. See section 6.2 on page 54.
INITIALIZING*
EEPROM is being loaded with factory defaults. This
occurs on first power up or if the user resets the
GSC400 to factory defaults from the PC Interface.
KEY BOARD FAILURE
This is an internal GSC400 failure. Try to power
cycle the GSC400. If the failure occurs repeatedly the
unit could be defected.
LOCKED ROTOR
Cranking attempt failed on locked rotor. See section