Table 9 – Submenus of the Advanced Menu
J1939 Setup
Manufacturer
John Deere, Volvo, Cummins,
Yanmar, Detroit Diesel, Others
Loss of ECM
Enable, Disable
Display Group 1
Enable, Disable
Display Group 2
Enable, Disable
DTC Display
Disable, Enable
Active DTC Log
Disable, Enable
Read Stored DTC
Disable, Enable
Auto Power ECM
Disable, Enable
ECM Power Delay
5-30 seconds
Cummins Idle
Disable, GCP Enable, GC1 Enable
High Engine Tmp
Input Pin
Disable, Analog 2-7
Signal Source
J1939, Switch input, Sender 1, 2, or 3
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Fahrenheit, Celsius
Warning Level
10-265°F, 10-265°C
Failure Level
10-265°F, 10-265°C
Oil Pressure
Input Pin
Reserve, Analog 2-7
Signal Source
J1939, Switch input, Sender 1, 2 or 3
Bypass Delay
10-60 Seconds
Switch Setting
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
PSI, KPa
Warning Level
0-90 PSI, 0-90 KPa
Failure Level
0-90 PSI, 0-90 KPa
Fuel Level
Input Pin
Reserve, Analog 2-7
Signal Source
Switch input, Sender
Bypass Delay
10-60 Seconds
Switch Setting
GND = Warning, OPEN = Warning,
GND = Fail, Open = Fail
Shorted Sender
Disable, Warning, Shutdown
Open Sender
Disable, Warning, Shutdown
Units
Percentage
Warning Level
0-90%
Failure Level
0-90%
0% Fuel Level
0-1000 Ohms (data sheet or measured
value)
25% Fuel Level
0-1000 Ohms (data sheet or measured
value)
50% Fuel Level
0-1000 Ohms (data sheet or measured
value)
75% Fuel Level
0-1000 Ohms (data sheet or measured
value)
100% Fuel Level
0-1000 Ohms (data sheet or measured
value)