96 of 105
start signal active or not active, please
read the register 40100 for system
state.
40111
Digital Output
0~2047
R (Read
Only)
Status of controller outputs. 0
corresponds to output OFF or NOT
ACTIVE, while a 1 corresponds to output
ON or ACTIVE.
Bit0 = Output A
0 = OFF, 1 =
ACTIVE
Bit1 = Output B
0 = OFF, 1 =
ACTIVE
Bit2 = Output C
0 = OFF, 1 =
ACTIVE
Bit3 = Output D
0 = OFF, 1 =
ACTIVE
Bit4 = Output E
0 = OFF, 1 =
ACTIVE
Bit5 = Output F
0 = OFF, 1 =
ACTIVE
Bit6 = Output G
0 = OFF, 1 =
ACTIVE
Bit7 = Output H
0 = OFF, 1 =
ACTIVE
Bit8 = Extra Relay
0 = OFF, 1 =
ACTIVE
Bit9 = Fuel Relay
0 = OFF, 1 =
ACTIVE
Bit10 = Crank Relay
0 = OFF, 1 =
ACTIVE
Advanced Modbus register support
1.
ENGINE-GENERATOR PARAMETERS
(Read Only)
Running parameters will update every 1 second. The engine speed, high engine temperature, low
engine temperature, oil pressure, and fuel level parameters display 0xFF01 if not available (if source
is J1939). The six sender inputs (High Engine Temperature, Low Engine Temperature, Fuel Level,
Oil Pressure, Oil Level, and Fuel In Basin) parameters display 0xFF00 if set to switch or disabled.
Summary of Contents for GSC400 Series
Page 15: ...Figure 4 General GSC400 System Wiring Diagram ...
Page 16: ...Figure 5 Digital IO Example ...
Page 105: ...105 of 105 ...