The GSC400 controller requires a neutral reference. All voltages are measured line to
neutral and then converted for display as line to line if required unless Voltage Group 1 is
selected with the two wire option in which case only Line to Neutral is displayed.
Figure 10 – Three-wire versus four wire delta generator configurations
6.4. .1
Voltage Select Inputs
It is
e or two of
e digital inputs to
Volt Select 1
and
Volt Select 2
. This allows the GSC400 to
utomatically re-configure its voltage display as well as warning/shutdown trip points
s and currents. This is useful for mobile generators where the
oltage selections can be selected via a CAM switch.
2
possible to automatically choose between each configuration by setting on
th
a
relating to AC voltage
v
Warning
: The Voltage Select Inputs override the
Voltage Group
submenu parameter in
the AC Voltage menu.