Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
10%
Failure Level
5%
Fuel In Basin
Input Pin
Disable
Signal Source
Switch
Bypass Delay
11 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Percentage
Warning Level
2%
Failure Level
5%
Low Engine
Temperature
Input Pin
Disable
Signal Source
Switch
Bypass Delay
10 Seconds
Switch Setting
SW Closed = Fail
Shorted Sender
Disable
Open Sender
Disable
Units
Fahrenheit
Warning Level
10ºF
Spd Sensing
Signal Source
Generator Output
Rated Freq
60 Hz
Rated RPM
1800 RPM
Over Speed Warn
1950 RPM
Over Speed Fail
2050 RPM
Under Speed Warn
1650 RPM
Under Speed Fail
1550 RPM
AC Frequency
Frequency Disconnect
22 Hz
Over Freq Warn
70 Hz
Over Freq Fail
75 Hz
Under Freq Warn
50 Hz
Under Freq Fail
45 Hz
A/C Voltage
Voltage Source
Enable
Voltage Display
Line-Neutral
Voltage Group
Group #1 (Single)
Over Volt Warn 1
250 VAC
Over Volt Fail 1
260 VAC
Under Volt Warn 1
230 VAC
Under Volt Fail 1
220 VAC
Over Volt Warn 2
220 VAC
Over Volt Fail 2
230 VAC
Under Volt Warn 2
195 VAC
Under Volt Fail 2
185 VAC
Over Volt Warn 3
500 VAC
Over Volt Fail 3
520 VAC
Under Volt Warn 3
460 VAC
Under Volt Fail 3
440 VAC
Over Volt Warn 4
630 VAC