98 of 105
Reading 318 corresponds
to 31.8V
40175
PCB Board
Temperature
-55 ~ 130
Signed
Integer 16 bit
R
1 bit 0.1C
Reading 1000 corresponds
to 100.0C
Positive or negative values
can be identified by
reading the high byte of
MSB. A 1 in bit 15
corresponds to a negative
number while a 0
corresponds to a positive
number
C
40176
Current Run time
(Total run time on active
running event).
NOTE: Timer is reset to
Zero after active running
event has been terminated
(OFF or AUTO mode
waiting to start)
0 ~ 6553.5
R
1 bit 0.1 hour
65535 corresponds to
6553.5Hs
Hours
40177 ~
40178
Engine Hours (old
way – use registers
40172/40173 instead)
0~255999.9
R
Total Accumulated
running hours, the reading
in 40177, 1 bit equal to 0.1
hour. The reading in
40178, 1 bit equal to 1000
hours. So the total hours =
40178
* 1000 +
40177
/10
Hours
40145
Maintenance Time
-1000 ~
+1000
Signed Integer
16 bit
R
The unit is 0.1 hour (1 bit = 0.1 hour);
Positive values count down the hours to
next maintenance. Negative values count
up the hours since maintenance should
have been performed. Positive or
negative values can be identified by read
the high byte of MSB. A 1 in bit 15
corresponds to a negative number while a
0 corresponds to a positive number.
2. EVENTS HISTORY LOG