99 of 105
Read Previous Entry
0x6C93
(27795)
W
40130
Read Next Entry
0x639C
(25500)
W
Write control command to holding
register address.
The controller will check the log request every 1 second. Each time a new command is received, the
controller will scroll either down or up one message (until it reaches either the bottom or top of the
message log), one message and update the log content in address 40131 to 40141. Once at the top of
the log, registers 40131 to 40141 are not changed if a “Read Previous Entry” command is received.
Once at the bottom of the log, registers 40131 to 40141 are not changed if a “Read Next Entry”
command is received. After 20s of receiving further commands in register 40130, all registers are
cleared (i.e. set to 0).
40131
Log Type
Only
supports the
values listed
in format
column.
R
1 Internal reserved 1 ( ADE Read )
2 Internal reserved 2 ( KEYBOARD)
3 Internal reserved 3 ( ADC read )
4 Internal reserved 4 ( RS485 )
5 Internal reserved 5 ( RS232 )
6 Internal reserved 6 ( ADE Write )
7 Internal reserved 7 ( TLE6230 )
8 Internal reserved 8 ( EEPROM )
9 (Reserved).
10 HIGH ENGINE TEMPERATURE
11 LOW OIL PRESSURE
12 UNDER SPEED
13 OVER SPEED
14 LOW FUEL LEVEL
15 LOW BATTERY
16 LOW COOLANT
17 OVER CRANK
18 OVER VOLTAGE
19 UNDER VOLTAGE
20 OVER CURRENT
21 EPS LOADS ERROR
22 LOW AIR PRESSURE
23 LOW HYDRAULIC
24 LOW OIL LEVEL
25 LOCKED ROTOR
26 HIGH BATTERY
27 LOSS OF ECM COMMUNICATION
28 OPEN ENG TEMPERATURE
29 SHORT ENG TEMPERATURE