18 of 105
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
Input H -
GND
1
18
7mA
Configurable
1, 3
Input G -
GND
2
18
7mA
Configurable
1, 3
Input F -
GND
3
18
7mA
Configurable
1, 3
Input E -
GND
4
18
7mA
Configurable
1, 3
Input D -
BAT
5
18
7mA
Configurable
2, 3
Input C - BAT
6
18
7mA
Configurable
2, 3
Input B - BAT
7
18
7mA
Configurable
2, 3
Input A -
BAT
8
18
7mA
Configurable
2, 3
Emer. Stop
9
18
7mA
Allows Manual
Emergency Stop (Open
= Active)
Start/Stop
(Remote Start
Contacts)
10
18
7mA
Allows Manual
Start/Stop of Engine
(Active = Start, Inactive
= Stop)
Ground
11
18
7mA
Ground
Ground
12
18
7mA
Ground
Digital
Inputs
1
Ground input to generate logic high.
2
Tie input to b to generate logic high.
3
See Table 15 on page 67 for possible selections.
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
+ V Bat
1
18
1.5A
Positive Battery Voltage
Output A
2
18
200mA
Configurable
*
Output B
3
18
200mA
Configurable
*
Output C
4
18
200mA
Configurable
*
Output D
5
18
200mA
Configurable
*
Output E
6
18
200mA
Configurable
*
Output F
7
18
200mA
Configurable
*
Output G
8
18
200mA
Configurable
*
Output H
9
18
200mA
Configurable
*
+ V Bat
10
18
1.5A
Positive Battery Voltage
Digital
Outputs*
*See Table 14 on page 64 for possible selections.
These are sinking outputs (i.e.
switched to ground).