76 of 105
Over Volt Fail 4
650 VAC
Under Volt Warn 4
570 VAC
Under Volt Fail 4
550 VAC
A/C Current
Current source
Enable
Turns Ratio
100A:5A
Over Current Warn 1
90 A
Over Current Fail 1
100 A
Over Current Warn 2
80 A
Over Current Fail 2
90 A
Over Current Warn 3
20 A
Over Current Fail 3
25 A
Over Current Warn 4
15 A
Over Current Fail 4
20 A
Engine Logic
Delay to Start
0 seconds
Pre-heat Time
0 seconds
Crank Time
15 seconds
MidHeat Time
0 seconds
Crank Rest Time
15 seconds
Crank Attempts
3
Fuel Crank Rest
Enable
False Restart
Enable
Post-Heat Time
0 seconds
ETS On Duration
0 seconds
Warm-up Time
600 seconds
Crank Disconnect
650 RPM
Cool Down Delay
0 seconds
Crank Oil pres
10 PSI
Digital Output Setup
All selections apply to
each individual output
Extra Relay
Disable,
Output 1
Disable
Output 2
Disable
Output 3
Disable
Output 4
Disable
Output 5
Disable
Output 6
Disable
Output 7
Disable
Output 8
Disable
Exerciser setup
Exerciser Enable
Disable
Run Duration
30 minutes
Pre-Alarm Delay
5 minutes
Repeat Frequency
336 hours (14 days)
Start Hour
12
Start Date
8
Digital Input Setup
All selections apply to
each individual input
Input 1 (Bat)
Disable
Input 2 (Bat)
Disable
Input 3 (Bat)
Disable
Input 4 (Bat)
Disable
Input 5 (Gnd)
Disable
Input 6 (Gnd)
Disable
Input 7 (Gnd)
Disable