48 of 105
Over Volt Fail 2
0-700 VAC
Under Volt Warn 2
0-700 VAC
Under Volt Fail 2
0-700 VAC
Over Volt Warn 3
0-700 VAC
Over Volt Fail 3
0-700 VAC
Under Volt Warn 3
0-700 VAC
Under Volt Fail 3
0-700 VAC
Over Volt Warn 4
0-700 VAC
Over Volt Fail 4
0-700 VAC
Under Volt Warn 4
0-700 VAC
Under Volt Fail 4
0-700 VAC
A/C Current
Current source
Disable, Enable
Turns Ratio
5-5000A:5A
Over Current Warn 1
0-6500 A
Over Current Fail 1
0-6500 A
Over Current Warn 2
0-6500 A
Over Current Fail 2
0-6500 A
Over Current Warn 3
0-6500 A
Over Current Fail 3
0-6500 A
Over Current Warn 4
0-6500 A
Over Current Fail 4
0-6500 A
Hi Wye Current
100%, 50%
Cur Warn Latch
Disable, Enable
Engine Logic
Delay to Start
0-60 seconds
Glowplug Time
0-60 seconds
Crank Time
3-60 seconds
MidHeat Time
0-60 seconds
Crank Rest Time
1-60 seconds
Crank Attempts
1-60
Fuel Crank Rest
Disable, Enable
False Restart
Disable, Enable
Post-Heat Time
0-60 seconds
ETS On Duration
0-30 seconds
Warm-up Time
0-600 seconds
RPM Disconnect
100-2000 RPM
Cool Down Delay
0-600 seconds
Crank Oil pres
0-90 Psi
Digital Output Setup
All selections apply to
each individual output
Extra Relay
Disable, Warm-Up, ETS,
Output A
Glowplug, Cooldown,
Output B
Over Crank , High Temp Fail ,
Output C
High Temp warn, Low Oil Fail ,
Output D
Low Oil Warning, Under RPM Fail,
Output E
Under RPM Warn, Over RPM Fail
Output F
Over RPM Warn, Low Fuel Fail
Output G
Low Fuel Warn, Battery Fail,
Output H
Battery Warn, Low Coolant Fail,
Low Coolant warn, Not in Auto,
Failure, Crank Rest,
Engine Running, Crank On,
Exerciser Alarm, Recharge Alarm