3 of 105
GSC400 Specifications
VDC Rating
12/24 VDC
Standby Current
Consumption
50 mA @ 12 VDC
Operating Temp
-40°C to +85°C (-40°F to +185°F)
LCD Operating
Temp***
-20
0
C to 70
0
C (-4
0
F to +158
0
F)
Function
Selection
Range
Speed Sensing
Generator pickup
Magnetic pickup
0-300vac, 0-3600rpm
0-300vac, 0-3600rpm
Voltage Sensing
Single phase,
Three phase,
Delta, Wye
Max 700vac, +/- 1%
Max 700vac, +/- 1%
Max 700vac, +/- 1%
Current Sensing*
Enable/Disable
Max 5A, +/- 2%
Frequency Sensing
Enable/Disable
1 – 100 HZ
Engine Temp
GND=Fail, Open=Fail
10-265°F, 10-265°C
Oil Pressure
GND=Fail, Open=Fail
0-90 PSI, 0-90 Kpa
Oil Level
GND=Fail, Open=Fail
0-90%
Fuel Level
GND=Fail, Open=Fail
0-100%
Engine Logic
Delay to start
Pre-heat
Crank
Rest Time
Mid Heat
Crank attempts
False restart
Post heat
Warm-up
Cooldown
Crank oil pressure
Crank Disconnect
0 – 60 seconds
0 – 60 seconds
3 – 60 seconds
1 – 60 seconds
0 – 60 seconds
1-60 tries
Enable, Disabled
0 – 60 seconds
0 – 600 seconds
0-600 seconds
0-90 KPa
100-2000 RPM
Analog Input
Input 2 (Low Z, Gain = 1)
Input 3,4 (Low Z, Gain = 3)
Input 5,7 (High Z, Gain =3)
Input 6 (High Z, Gain = 1)
Gnd=Fail, Open=fail, 7mA Max
Note: On LS/LX controllers
Input 2 is High Z, Gain = 3 and
Input 6 has a gain of 3.
Digital Input
Input A-D (Sw to Bat)
Input E-H (Sw to Gnd)
Bat=Fail, 7mA Max
Gnd=Fail, 7mA Max
Digital Output
Output A-H
Extra Relay
200 mA Max
40A Max
Exerciser
Enable, Disable
10-240 Minutes
Battery Recharge
Enable, Disable
10-240 Minutes
Function
Selection
Range
Password 4-Digit
0-9
LCD Display
128x64 Graphic display, Backlit, 60° viewing angle
LED Display
Red, Green, Yellow LED representation, Daytime Visible, 60° viewing angle
Programming
Manual, Software, Field upgradeable
J1939 Interface
Low emission capable
Relays**
Replaceable 40A relays for Crank, Fuel, Extra output. 12 or 24VDC Coil
Dimensions
W x H x D, 139 x 113 x 65 mm (5.47 x 4.45 x 2.56 in.)
Weight
0.45 Kg (1.0 Lb)
*Use of Industry Standard CT Required. ** 40A output at room temperature. *** The LCD
display will exhibit color and response time changes at high and low temperatures respectively
but will not be damaged as long as within Operating Temp.
Summary of Contents for GSC400 Series
Page 15: ...Figure 4 General GSC400 System Wiring Diagram ...
Page 16: ...Figure 5 Digital IO Example ...
Page 105: ...105 of 105 ...