65 of 105
activated. See
section 6.5.1
for more details. The number of
crank attempts is set in the engine logic menu.
High Temp Failure
This turns on the digital output if the High Engine Temperature
Failure is activated. See
section 6.2
for more details.
High Temp Warning
This turns on the digital output if the High Engine Temperature
Warning is activated. See
section 6.2
for more details.
Low Oil Failure
This turns on the digital output if the Low Oil Pressure Failure is
active. See
section 6.2
or
section
6.8
for more details.
Low Oil Warning
This turns on the digital output if the Low Oil Pressure Warning is
activated. See
section 6.2
for more details.
Under Speed Failure
This turns on the digital output if the Under Speed Failure is
activated. See
section 6.3
for more details.
Under Speed Warning
This turns on the digital output if the Under Speed Warning is
activated. See
section 6.3
for more details.
Over Speed Failure
This turns on the digital output if the Over Speed Failure is
activated. See
section 6.3
for more details.
Over Speed Warning
This turns on the digital output if the Over Speed Warning is
activated. See
section 6.3
for more details.
Low Fuel Failure
This turns on the digital output if the Low Fuel Failure is
activated. See
section 6.2
for more details.
Low Fuel Warning
This turns on the digital output if the Low Fuel Warning is
activated. See
section 6.2
for more details.
Battery Failure
This turns on the digital output if the Low or High Battery Failure
is activated. See
section 6.9
for more details.
Battery Warning
This turns on the digital output if the Low or High Battery
Warning is activated. See
section 6.9
for more details.
Low Coolant Failure
This turns on the digital output if the Low Coolant Failure is
activated. This is controlled by the Low Coolant Digital Input
described in Table 15
in
section 6.8
.
Low Coolant Warning
Reserved for future use. Selecting this feature will have no effect.
Not In Auto
This turns on the digital output when the controller is not in the
Auto state.
Section 5.3
describes the various states of the
controller.
General Failure
This turns on the digital output when any failure is active.
Crank Rest
This turns on the digital output when the controller is in the crank
rest state after a crank attempt. The crank rest duration is set in
the engine logic menu. See
section 6.5.1
for more details.
Engine Running
This turns on the digital output when the controller enters the run
state (crank success). The run state is described in
section
5.3
.
Engine Cranking
This turns on the digital output when the crank output is on. See
section 6.5.1
for more details.
Exerciser Alarm
This turns on the digital output when the engine/generator starts on
an exerciser event (
section
6.7
).
Battery Recharge Alarm
This turns on the digital output when the engine/generator starts on
a low battery event (
section
6.2
).
Under Voltage Warning
This turns on the digital output when the AC Under Voltage
Warning (
section 7.4
) is activated.
Over Voltage Warning
This turns on the digital output when the AC Over Voltage
Warning (
section 7.4
) is activated.
Over Current Warning
This turns on the digital output when the AC Over Current
Summary of Contents for GSC400 Series
Page 15: ...Figure 4 General GSC400 System Wiring Diagram ...
Page 16: ...Figure 5 Digital IO Example ...