Model:
Serial #:
Crane Commander Setting Sheet
(Sheet 1 of 2)
CODE
DESCRIPTION
RANGE
SET UNIT
HOIST
TRAVERSE
NOTE
FIELD
SETTING
Fn00
'Command Link' ID No.
0~32
-
1
1
Fn01
Primary Accel. Time
0.1-800.0 sec.
0.1 sec.
3 sec.
5 sec.
Fn02
Primary Decel. Time
0.1-30.0 sec.
0.1 sec.
3 sec.
5 sec.
Fn03
Max. speed limit divisor
1~30
0.1
1
1
Fn04
DEC. stall prevention
1~8
-
1
3
***
See code #79
0~100
-
0
1
**
Fn05
V/F Pattern Select
0~15
-
6
3
Fn06
Freq. Output Upper Limit
1-180Hz
0.1Hz
60 Hz
60 Hz
Fn07
Freq. Output Lower Limit
0-180Hz
0.1 Hz
2 Hz
0 Hz
Fn08
Multi- Function Output
0~2
-
2
0
Fn09
Set Frequency Approach
1-180Hz
0.1 Hz
3 Hz
5 Hz
Fn10
Control Mode Select
0~1
-
1
1
Fn11
Freq. Command Method
0: Keypad
1: TM2 VR Freq.
2: 5 speed
3: 2 step infinitely variable
4: 3 step infinitely variable
-
2
2
Fn12
ACC. stall prevention
1~8
-
1
3
***
ACC. stall current level
0-120~200%
1%
0
170%
**
Fn13
Fault Relay Preset
0~1
-
0
0%
Fn14
Reset set
0~1
-
0
0
Fn15
Slip compensation freq
0~5%
0.10%
0
0
Fn16
Direct Start Prohibit
0~1
-
1
1
Fn17
Speed 1
0-180Hz
0.1 Hz
6 Hz
6 Hz
Fn18
Speed 2
0-180Hz
0.1 Hz
15 Hz
15 Hz
Fn19
Speed 3
0-180Hz
0.1 Hz
30 Hz
30 Hz
Fn20
Speed 4
0-180Hz
0.1 Hz
45 Hz
45 Hz
Fn21
Speed 5
0-180Hz
0.1 Hz
60 Hz
60 Hz
Fn22
'Smooth Operator' curve Time
1
0-4 sec.
0.1 sec
0 sec.
0.5 sec.
Fn23
'Smooth Operator' curve Time 2 0-4 sec.
0.1 sec.
0 sec.
0.5 sec.
Fn24
Jog Frequency
0-180Hz
0.1 Hz
5 Hz
5 Hz
Fn25
Master Frequency
0-180Hz
0.1 Hz
5 Hz
5 Hz
Fn26
BIAS of TM2 analog input
0-180Hz
0.1 Hz
0 Hz
0 Hz
Fn27
Positive/Negative BIAS
0~1
-
0
0
Fn28
Max. Speed of analog input
1-180 Hz
0.1 Hz
60 Hz
60 Hz
Fn29
Hoist / Traverse 'Quick Set'
0-Hoist 1-Traverse
-
0
1
Fn30
External frequency mode
0~1
-
0
0
Constant speed stall Prevention
freq. level
1-180Hz
0.1 Hz
60 Hz
60 Hz
***
Constant speed stall level
0~160%
1%
160%
160%
**
Fn32
Constant speed stall Prevention
Dec. time
0.1-800 sec.
0.1 sec.
0.8 sec.
(3 sec.)
0.8 sec.
(3 sec.)
***
**
Fn33
Auto alternate Acc./Dec. time
0: Normal
1: 'Quick Change'
2: 'Rapid Stop'
3: Both 'Quick Change' and
'Rapid Stop'
-
0
1
Fn34
Auto restart Interval Time
0.1-800 sec.
0.1 sec.
5 sec.
5 sec.
Fn35
Auto restart times
0~10
-
0
0
Fn36
External TM2 Scan times
0~9999
-
105
105
Fn37
Max. frequency
50-180Hz
0.1 Hz
60 Hz
60 Hz
Fn38
Max. voltage ratio
0~100 %
0.10%
100%
100%
Fn39
Mid. frequency
1-180Hz
0.1 Hz
3 Hz
3 Hz
Fn40
Mid. voltage ratio
0~100%
0.10%
7.50%
7.50%
Fn41
Min. frequency
1-180Hz
0.1Hz
1 Hz
1 Hz
Fn42
Min. voltage ratio
0-100%
0.10%
7.5% (4.2%) 7.5% (4.2%)
***
**
Fn43
Carrier frequency
1440-3600 Hz
1 Hz
2880 Hz
2880 Hz
Fn31
Software version 10.6 or 20.4
CCSET1
* Only for Trolley / Bridge operation
** Only available on CC2110-2220, 4110-4220 models
*** Only available on CC204-275, 404-475 models
**** Only for Hoist operation