43
Fn13:
Fault relay preset
Fn13=0:
Fault relay is preset normally open. (N/O)
Fn13=1:
Fault relay is preset normally closed. (N/C)
When inverter is without power, contact is normally open. (N/O)
Fn14:
Reset (effective in both digital operator and remote control operation.
Fn10=0
or
Fn10=1
)
If
Fn14
is set to 0, inverter can't be reset via digital operator reset key or reset switch. (Terminal 11
of TM2 or terminal 5 of D61530 TB1) unless stop command is given.
Fn14=0:
Reset is invalid unless inverter is stopped.
Fn14=1:
Reset is effective any time.
Note: Important!
If the application condition allows, it is strongly recommended to disable (set
Fn14=0
) this function
to prevent injury to personnel and equipment damage.
Fn15:
Frequency slip compensation.
Provides increase or decrease in frequency based on load condition and motor slip.
Range: For hoists (Fn29=0) up; + slip compensation, down - slip compensation from 0-5% addi-
tional or less frequency output.
Range: For traverse (Fn29=1) + slip compensation only. Set range to match motor slip percentage.
Fn16:
Direct start prohibit. (effective in remote control only, Fn10=1)
If this function is set to 1, inverter will not start immediately after power switched on. Inverter must
acknowledge the lack of run command first.
WARNING: Important!
If the application condition allows, it is strongly recommended to set
Fn16
to 1 to prevent injury to personnel and equipment damage.
Fig. 5.3g
Fn12
example for CC 2110-2220 and 4110-4220
b) models CC 2110-2220/ CC 4110-4220 only.
Fn12=0:
Acceleration stall trip prevention is disabled.
Fn12
=120-200% level of motor current where stall occurs.
WARNING:
It is suggested to disable this function if the application must maintain the preset
acceleration time. ie: All hoists.