1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
50/105
15.2 D
EFAULT READ
-
OUT OF THE BOTTOM DISPLAY
To set the default value displayed on the bottom display:
1.
Set the parameter dP03 = 0, it means configurable;
2.
Select the dP02 parameter into the range 0..17 descripted here below:
PARAMETER
VALUE
DESCRIPTION
CORRESPONDING
LABEL
dP02=0
No display read out
No label
dP02=1
NTC temperature probe of the evaporator water inlet
Ein
dP02=2
NTC temperature probe of the evaporator water outlet 1 and 2
Out1
circuit 1
Out2
circuit 2
dP02=3
NTC temperature probe of the common evaporator water outlet
Eout
dP02=4
NTC temperature probe of the condenser water inlet
CIn1
circuit 1
CIn2
circuit 2
dP02=5
NTC temperature probe of the common condenser water inlet
Cin
dP02=6
NTC temperature probe of the condenser water outlet
Cou1
circuit 1
Cou2
circuit 2
dP01=7
NTC temperature probe of the common condenser water outlet
Cout
dP02=8
NTC temperature probe of the dynamic external air setpoint
Et
dP02=9
NTC temperature probe of the free cooling water inlet
FCIn
dP02=10
NTC temperature probe of the free cooling external air value
FCEt
dP02=11
NTC temperature probe of the remote terminal 1
trt1
dP02=12
NTC temperature probe of the remote terminal 2
trt2
dP02=13
NTC temperature probe of the combined defrost
dEF1
circuit 1
dEF2
circuit 2
dP02=14
NTC temperature probe of the condenser
Cdt1
circuit 1
Cdt2
circuit 2
dP02=15
Pressure probe of the condenser 4÷20mA - 0.5V
Cdt1
circuit 1
Cdt2
circuit 2
dP02=16
Pressure probe of the evaporator 4÷20mA - 0.5V
LP1
circuit 1
LP2
circuit 2
dP02=17
Clock
TOP DISPLAY: CUSTOM EXAMPLE
Parameter dP01=01. The default read out for the circuit 1 and the circuit 2 is the NTC probe value of the evaporator water inlet.
Parameter dP01=02. The default read out for the circuit 1 is the evaporator outlet 1 temperature, while for the circuit 2 is the evaporator
2 outlet temperature.
BOTTOM DISPLAY: CUSTOM EXAMPLE
Parameter dP02=03. The default read out for the circuit 1 and the circuit 2 is the NTC probe value of the evaporator water outlet.
Parameter dP02=14. The default read out for the circuit 1 is the condenser 1 temperature, while for the circuit 2 is the condenser 2
temperature.
15.3 F
ORCED READ
-
OUT OF THE TOP AND BOTTOM DISPLAY
To force the display read-out:
1. Set
the
dP03
parameter not equal to
0
2.
Select the value range 1..3
These configurations allow to show together two temperatures or two pressures of the same circuit in order to have an easier reading of
the measurements:
Par.
dP03 = 1
Top display: for both the circuits 1,2:
•
Evaporator water inlet, with the
Ein
label.
Bottom display: circuit 1:
•
Evaporator 1 water outlet, with the label
OuT1
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...