1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
AL 22
Maximum number of pump down alarm events per hour in start-up condition.
After this number the alarm is logged, displayed and signalled with alarm
relay + buzzer.
Always manual reset if AL22 = 0
Always automatic reset if AL22 =16
From automatic to manual reset if AL21 =1..15 and parameter AL23 config.
0 16
AL 23
Select if the pump down alarm must change from automatic to manual reset:
0= Always automatic reset
1= Manual reset after AL21 alarm events
0 1
Anti-freeze alarm in Chiller mode
AL 24
Minimum antifreeze setpoint in chiller (from –30 °C to AL24)
-30.0
-22
AL24
°C
°F
Dec
int
AL 25
Maximum antifreeze setpoint in chiller (from AL24 to 70 °C)
AL24
70.0
158
°C
°F
Dec
int
AL 26
Setpoint temperature for low anti-freeze alarm, low ambient temperature
(air/air), low temperature air outlet (air/air). From AL24 to AL25.
AL24 AL25 °C/°F
Dec/int
AL 27
Differential of alarm reset in Chiller mode for anti-freeze, low ambient air
temperature or low outlet air temperature alarms.
0
0
25.0
45
°C
°F
Dec
int
AL 28
Alarm delay for anti-freeze, low ambient air temperature or low outlet air
temperature. The temperature must be lower than AL26 for this time duration
before having the alarm event.
0 250
Sec
AL 29
Maximum number of alarm events anti-freeze, low ambient air temperature or
low outlet air temperature before changing from automatic to manual alarm
reset:
Always manual reset if AL29 = 0
Always automatic reset if AL29 = 16
From automatic to manual if AL29 = 1. .15
0 16
AL 30
Anti-freeze alarm configuration in chiller
0= to turn the compressors off when the anti-freeze control probe is lower
than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower
than AL26 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
0 1
Anti-freeze alarm in Heat pump mode
AL 31
Setpoint of the minimum limit in heat pump (va da – 30 °C a AL32)
-30.0
-22
AL31
°C
°F
Dec
int
AL 32
Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C)
AL31
70.0
158
°C
°F
Dec
int
AL 33
Anti-freeze alarm setpoint in heat pump
Setpoint temperature for low anti-freeze alarm, low ambient temperature
(air/air), low temperature air outlet (air/air). (from AL31 to AL32)
AL31 AL32 °C/°F
Dec/int
AL 34
Alarm differential in heat pump. To reset the anti-freeze, low ambient
Temperature (air/air), low temperature air outlet (air/air) alarms.
0
0
25.0
45
°C
°F
Dec
int
AL 35
Anti-freeze alarm delay in HP for low outlet air temperature (air/air)
Attention
If during the Stand-by or remote off there is an anti-freeze alarm event, and
the AL35 <>0, starting the heat pump mode, from keyboard or digital input. In
this case the anti-freeze alarm is aborted and the compressor starts for the
AL35 time to heat the air or the water.
After the AL35 time if the antifreeze probe value is still lower than AL33
setpoint, for maximum AL36 seconds, the unit is stopped and the anti-freeze
alarm is generated again.
0 250
Sec
AL 36
Anti-freeze alarm delay for low air ambient temperature or low outlet air
temperature in heat pump normal condition.
The detected temperature must be lower than AL33 for the time AL36 before
giving the alarm
0 250
Sec
AL 37
Maximum number of anti-freeze alarm events for low air ambient temperature
or low outlet air temperature in heat pump. It sets the alarm reset condition:
Always manual reset AL37 = 0
Always automatic reset AL37 = 16
From automatic to manual reset if AL37 = 1..15
0 16
AL 38
Anti-freeze alarm configuration in heat pump
0= to turn the compressors off when the anti-freeze control probe is lower
than AL33 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated.
1= to turn the compressors off when the anti-freeze control probe is lower
than AL33 (after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
0 1
Compressor high discharge temperature
AL 39
Compressor high discharge temperature setpoint
0
0
150
302
°C
°F
Dec / int
int
AL 40
Compressor high discharge temperature differential
0
0
25.0
45
°C
°F
Dec
int
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...