1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
37.1
OUTPUT STEP RELE
’
CONDENSER FAN
Par FA01 = 2
ON/OFF step regulation
N° 1 circuit with 4 step of ventilation
Step regulation
OUT relè
step n° 1
step n° 2
step n° 3
step n° 4
Out relè step n° 1
step
N° 1
ON
step
N° 1
OFF
step
N° 1
OFF
step
N° 1
OFF
Out relè step n° 2
step
N° 2
OFF
step
N° 2
ON
step
N° 2
OFF
step
N° 2
OFF
Out relè step n° 3
step
N° 3
OFF
step
N° 3
OFF
step
N° 3
ON
step
N° 3
OFF
Out relè step n° 4
step
N° 4
OFF
step
N° 4
OFF
step
N° 4
OFF
step
N° 4
ON
Par FA01 = 3
ON/OFF continuous step regulation
N° 1 circuito con quattro gradini di ventilazione
Continuous step regulation
OUT relè
Gradino n° 1
Gradino n° 2
Gradino n° 3
Gradino n° 4
Out relè step n° 1
step
N° 1
ON
step
N° 1
ON
step
N° 1
ON
step
N° 1
ON
Out relè step n° 2
step
N° 2
OFF
step
N° 2
ON
step
N° 2
ON
step
N° 2
ON
Out relè step n° 3
step
N° 3
OFF
step
N° 3
OFF
step
N° 3
ON
step
N° 3
ON
Out relè step n° 4
step
N° 4
OFF
step
N° 4
OFF
step
N° 4
OFF
step
N° 4
ON
37.2 PWM
OUTPUT FOR FAN CONTROL
If FA01=3 and the fan control boards are connected to the PWM outputs (TF1 and2) take note of the FA03 ,FA04 parameters.
The fan start-up is always made at the maximum speed for the time set in FA03, then the speed follows the probe value.
The F04 delay, in micro – seconds, allows to adjust the output for each kind of the fan motor.
If FA01=3, when the compressor starts-up and the proportional regulation requires to turn off the fan (cut-off), if FA14
≠
0 the fan is forced
at the minimum speed for the time set in FA14 itself. if FA14=0 the function is disabled.
37.3
CONDENSING UNIT
:
COMMON OR SEPARATE
FA05
defines the condenser unit
Par.
FA05
type of condenser
0= Common condenser unit.
1= Separate condenser units.
If Pa FA05= 0 the outputs, configured as condensing fan control, will follow the same regulation algorithm.
The regulation includes:
•
CHILLER mode:
the maximum probe value compared between the temperature/pressure probe of the two circuits.
•
HEAT PUMP (no evaporator probe configured)
the minimum probe value compared between the condenser
temperature/pressure probe of the two circuits.
•
HEAT PUMP (evaporator probe configured)
the minimum probe value compared between the evaporator temperature/pressure
probe of the two circuits.
If par. FA05 = 1 and if the evaporating pressure probe are not configured, the fan output controls are separated and are controlled by
the condenser temperature/pressure probes. When the evaporator probes are configured, in heat pump the ventilation is controlled by
these transducers.
37.4 G
RAPH
: P
ROPORZIONAL REGULATION OF CONDENSER FANS
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...