1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
86/105
ACF6
•
The total number of compressor of the 2 circuits ( CF04 + CF05 ) is:
√
> 6
√
> 4 with no direct compressor start-up (CO10
≠
0) or the number of steps is
≠
0 (CF06),
√
> 2 and the intermittent valve is configurated with ON (CO08) and OFF (CO09 )
≠
0
•
Pump-down function but at least in one circuit
√
The pump-down solenoid relay is not present
√
No pump-down pressure switch or evaporating probe when
the pump-down is enabled with unit in start
Or
No low pressure switch configurated.
•
The compressor configuration with CF04 and CF05 but not the relay outputs:
√
Main
√
Intermittent valve when enabled with the ON / OFF time, CO08 / CO09
≠
0
√
When the by-pass time
≠
0 and there is no partialization or by-pass valve configured
√
Motor part_2 / centre of the star with part-winding or star-delta
√
The necessary step valve configurated
•
One relay is configured
√
Too much compressors
√
Intermittent valve when ON / OFF time CO08 / CO09
≠
0
√
By-pass gas when the by-pass = 0
√
Compressor Motor coil 2 / center of the star with direct compressor start-up
•
Too much step valve
ACF7
Evaporator pump
√
Enabled
(CO16
≠
0
) but the relay is not configured
√
Not enabled (CO16 =
0
) but the relay is configured
Condenser pump
√
Enabled
(CO21
≠
0
) but the relay is not configured
√
Not enabled (CO21 = 0) but the relay is configured
ACF8
•
Thermoregulation probe
The thermoregulation probe (in chiller with ST09, in heat pump when enabled with ST10) is
not properly configurated (it does not exist or it is not a NTC)
ACF9
•
Recovery cycle enabled Par. rC01
≠
0
only some of these resources are configured: condensing probe, recovery digital input,
recovery relay, or no outputd is configured.
Origin
Wrong programming
Reset
Correctly programming
Restart
Automatic
Icon
Blinking
Action
Alarm relay + buzzer ON
41.11 A
RT
F C
LOCK FAILURE
Label o the display
ArtF
(clock failure)
Origin
Clock chip failure
Reset
Change clock chipset
Restart
Manual in function menu
Icon
Blinking
Action
Alarm relay + buzzer ON
Regulation
Loads
Not changed
Energy saving
Disabled if based on RTC
Unit ON/OFF
Disabled if based on RTC
Summary of Contents for ichill IC260L