1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
7.
Repeat operation 1 – 5 to reset the other alarms.
17.3 C
OMPRESSOR OVERLOAD PASSWORD
.
The default value is
0
to change this value enter Pr3 level under the AL parameter family
17.4 A
LARM LOG LIST
ALOG FUNCTION TO SEE THE ALARM LOG
The function and the alarm codes are visible only if there are alarm events. If many events are active at the same time the list displayed
by increasing order.
Enter the function Menu
1. Select
ALOG
2. Push
SET
one time. Nothing happens if there are no active alarm events.
3.
The bottom display shows the alarm label, the top display shows the a number in the range 00 to 99.
4.
Use the UP or DOWN keys to scroll the list.
5.
To exit the ALOG function push MENU or wait the timeout.
17.5
E
RASE THE
A
LARM LOG LIST
ALOG FUNCTION TO ERASE THE LOG LIST
1.
Enter the function Menu.
2. Use
the
UP
or
DOWN
keys to select ALOG on the bottom display.
3.
Push on e time the
SET
key.
4.
Within the ALOG function select with
UP
or
DOWN
keys, the
ArSt
label on the bottom display while the top display shows PAS.
5. Push
SET
: the bottom display shows
PAS
and the top display a blinking 0.
6.
Insert the password (See parameter family AL)
7.
If the password is OK the label
ArST
blinks for 5 seconds then the display returns to normal condition read-out (probes).
8.
If the password is not correct the display shows
PAS
again. in any case is possible to scroll the list with
UP
or
DOWN
9.
To exit push the M key one time or wait the timeout.
17.6 P
ASSWORD VALUE OF THE ALARM LIST
The default value is
0
to change this value enter Pr3 level under the AL parameter family.
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL ANY NEW ALARM WILL
ERASE THE OLDEST.
17.7 D
ISABLE
–
ENABLE A SINGLE CIRCUIT
Through the instruments keyboard is possible to completely disable a single circuit for maintenance or to use just a cooling part of of the
unit.
CrEn FUNCTION enables – disables a circuit from keyboard.
Label involved with CrEn function:
Cr1E = circuit 1, Cr2E = circuit 2
DISABLE A CIRCUIT
Enter the function Menu
1. Use
UP
or
DOWN
keys to select CrEn on the bottom display
2. Push
SET
key: the bottom display =
Cr1E
, top display =
En
.
3.
Select the circuit 1 or 2 with UP or DOWN (Cr1E or Cr2E).
4. Push
SET
key for 3 seconds when one of the two Cr1E, Cr2E label are displayed. The top display shows the
En
blinking label,
use the UP or DOWN to change in
diS
(Disabled) or En (Enabled). then push SET key to confirm the new selection. The display
shows next circuit status.
5.
To exit the CrEn function push MENU key or wait the timeout.
17.8 R
EAD
-
OUT OF A
C
IRCUIT
N
OT ENABLED
If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement selected.
Circuit 1 = diS the bottom display shows
b1dS
= circuit 1 disabled.
Circuit 2 = diS the bottom display shows
b2dS
= circuit 2 disabled.
The
b2dS
label appears only if the 2
nd
circuit is configured,
17.9 E
NABLE OR DISABLE A SINGLE COMPRESSOR
Through the instruments keyboard is possible to disable a single compressor for maintenance or to lock it when malfunctioning .
COEn FUNCTION
compressors running status.
Label involved in COEn function:
CO1E = Compressor 1 status… CO6E = Compressor 6 status
The COEn function uses only the compressors configured by the corresponding output parameters.
Enter the function Menu
1. Use
the
UP
or
DOWN
keys to select COEn.
2.
Push SET key: bottom display = CO1E, top display = En
3.
Select the compressor with UP or DOWN: CO2E - CO3E - CO4E - CO5E - CO6E if available.
4.
Push SET for 3 seconds when the label corresponds to the compressor to disable: CO1E - CO2E - CO3E - CO4E - CO5E - CO6E.
The top display shows the blinking En label, use the UP or DOWN key and change to diS (Compressor disabled) or En
(compressor enabled) then push SET to confirm, the display shows next item.
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...