1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
FA 16
Minimum speed for condenser fan in Heat Pump mode.
To set the minimum fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 17
Maximum speed for condenser fan in Heat Pump mode.
To set the maximum fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 18
Proportional speed control
FA01 = 4
Temperature or pressure limit to enable the minimum speed FA16
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 19
Proportional speed control
FA01 = 4
Temperature or pressure limit to enable the maximum speed FA17
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 20
Proportional speed control
FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 21
Proportional speed control
FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential
to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 22
Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential
to keep the minimum fan speed.
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 23
Night speed in Heat pump. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
30 100 %
Hot start
FA 24
Hot start setpoint
-30.0
-22
70.0
158
°C
°F
Dec
int
FA 25
Hot start differential
0.0
0
25.0
45
°C
°F
Dec
int
3 / 4 step condenser Fan in Chiller mode
FA 26
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 27
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
3 / 4 step condenser Fan in heat pump
FA 28
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 29
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Antifreeze heaters – Integration heating - boiler
Parameter
Description
min
max
m. u. Risoluzione
Ar 1
Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 2
Regulation band for antifreeze in Chiller mode.
0.1
0
25.0
45
°C
°F
Dec
Int
Ar 3
Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 4
Regulation band for antifreeze in HP mode.
-30.0
-22
70.0
158
°C
°F
Dec
int
Ar 5
Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control
1= ON with thermoregulation and during the defrosting cycle
0 1
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...