43 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION
The alarm codes are made of letters and numbers to define the different typologies:.
43.1 ALARM: “A”
TYPE AND CORRESPONDING OUTPUT OFF
Alarm
Code
Alarm description
Compressor
Anti freeze
heaters
Boiler
Support
heaters
Evap.
Pump.
Supply fan
Condens
er Pump
Ventilaz.
cond.
Cir1 Cir2
Auxiliary
relay
AP1
Probe PB1 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP2
Probe PB2 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP3
Probe PB3 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP4
Probe PB4 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP5
Probe PB5 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP6
Probe PB6 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP7
Probe PB7 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP8
Probe PB8 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP9
Probe PB9 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
AP10
Probe PB10 Alarm
Yes
Yes
(1)
Yes
Yes Yes
(2)
ALti
Low air temperature of the evaporator inlet (air / air unit) Alarm
AEFL
Evaporator flow alarm
Yes
Yes (boiler)
Yes
(3)
Yes
ACFL
Condenser flow alarm
Yes
Yes
(3)
Yes
AtSF
Fan supply overload alarm
Yes
Yes
Yes
Yes
AEUn
Unloading signalling from evaporator
AtE1
Water pump overload alarm evaporator 1
Yes
(4)
Yes
(boiler)
(5)
Yes
Yes
AtE2
Water pump overload alarm support evaporator 2
Yes
(4)
Yes
(boiler)
(5)
Yes
Yes
AtC1
Water pump overload alarm condenser 1
Yes
(4)
Yes Yes
AtC2
Water pump overload alarm support condenser 2
Yes
(4)
Yes Yes
AEP1
Water pump maintenance evaporator 1
AEP2
Water pump maintenance support evaporator 2
ACP1
Water pump maintenance condenser 1
ACP2
Water pump maintenance support condenser 2
ArtC
Clock alarm
Atr1
Remote terminal n° 1 configured but not connected
Atr2
Remote terminal n° 2 configured but not connected
ArtF
clock failure
ALOC
Generic alarm with unit stopped
Yes
Yes
Yes
Yes
Yes
AEE
Eeprom alarm
Yes
Yes
Yes
Yes
Yes
ACF1
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF2
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF3
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF4
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF5
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF6
Configuration alarm
Yes
Yes
Yes
Yes
Yes
ACF7
Configuration alarm
Yes
Yes
Yes
Yes
Yes
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...