1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
36/105
US 7
Auxiliary setpoint 2 (See graph and auxiliary relay functions)
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 8
Auxiliary differential 1 (See graph and auxiliary relay functions)
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Condenser fan
Parameters
Description
min
max
M. U. Resolution
FA 1
Fan configuration output
0 = Not enabled
1 = Always on
2 = ON/OFF regulation with steps
3 = ON/OFF Continuous regulation
4 = Proportional speed control
0 4
FA 2
Fan operating mode
0= Dependent from the compressor
1= Independent from the compressor
0 1
FA 3
If the condenser fan control is the triac output, when the regulation starts the
trigger output will drive the condenser fan at the maximum voltage for the time
FA 3 then, then the regulation will follow the temperature/pressure of the
probe.
0 250
Sec
FA 4
Phase shifting of the fan motor
0 8
Micro
Sec
250
µ
s
FA 5
Number of condensing circuits
0= one condenser circuit
1= tow condenser circuits
0 1
FA 6
Pre-ventilation time before turning on the compressor in chiller mode.
To turn on the fan at the maximum speed before the compressor and reduce
the successive condensing temperature/pressure increasing. (only if FA01=4)
0 250
Sec
Fan in Chiller mode
FA 7
Minimum speed for condenser fan in Chiller mode.
To set the minimum fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 8
Maximum speed for condenser fan in Chiller mode.
To set the maximim fan speed percentage value (30..100%), it is related to
the fan power supply.
30 100 %
FA 9
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the minimum speed FA 7
ON/OFF regulation FA01 = 2/3
SETpoint step n° 1
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 10
Proportional speed control FA01 = 4
Temperature or pressure limit to enable the maximum speed FA 8
ON/OFF regulation FA01 = 2/3
SETpoint step n° 2
-30.0
-22
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 11
Proportional speed control
FA01 = 4
Proportional band for condenser fan control in chiller
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 12
Proportional speed control
FA01 = 4
CUT-OFF differential in chiller. To set a temperature/pressure differential to
stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 13
Over ride CUT- OFF in chiller. To set a temperature/pressure differential to
keep the minimum fan speed.
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 14
CUT-OFF time delay. To set a time delay before activating the CUT-OFF
function after the fan start-up.
If after the compressor start-up the proportional regulator requires to turn off
the fan (cut-off) and FA14
≠
0, the fan is on at the minimum speed for the time
set in this parameter. If FA14=0 the function is disabled.
0 250
Sec
FA 15
Night speed in chiller. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
30 100 %
Fan in Heat pump mode
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...