1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
24/105
7.14 R
EMOTE
P
ANELS
VI620 – VI820
The instrument receives up to two remote panels. Using the remote panels provided with the ambient NTC probe the display
measurement, and the control can be managed directly by this probe. Use shielded cable for the connection up to 150mt maximum. In
case of communication failure the upper display shows “
noL”
(no link).
Use the CAB/CJ30 to interface the ichill connector to the shielded cable.
•
Remote panel VI620 for models IC260L – IC261L
•
Remote panel VI820 for models 200 L IC280L – IC281L
8 ANALOG AND DIGITAL OUTPUT CONFIGURATION
8.1 A
NALOG INPUT
P
B
1 - P
B
2 - P
B
7 - P
B
8 - P
B
9 - P
B
10
Parameters involved:
CF08 =
Configuration PB1
CF09 =
Configuration PB2
CF14 =
Configuration PB7
CF15 =
Configuration PB8
CF16 =
Configuration PB9
CF17 =
Configuration PB10
0. Not
enabled
1. Temperature
probe
PTC
for compressor #1 discharge
2. Temperature
probe
PTC
for compressor #2 discharge
3. Temperature
probe
PTC
for compressor #3 discharge
4. Temperature
probe
PTC
for compressor #4 discharge
5. Temperature
probe
PTC
for compressor #5 discharge
6. Temperature
probe
PTC
for compressor #6 discharge
7. Temperature
probe
NTC
for evaporator inlet
8. Temperature
probe
NTC
for evaporator #1 outlet
9. Temperature
probe
NTC
for evaporator #2 outlet
10. Temperature
probe
NTC
for common evaporator outlet
11. Temperature
probe
NTC
for common hot water condenser / recovery inlet
12. Temperature
probe
NTC
for hot water of the condenser / recovery circuit #1 inlet
13. Temperature
probe
NTC
for hot water of the condenser / recovery circuit #2 inlet
14. Temperature
probe
NTC
for hot water of the condenser / recovery circuit #1 outlet
15. Temperature
probe
NTC
for hot water of the condenser / recovery circuit #2 outlet
16. Temperature
probe
NTC
for hot water of the condenser / recovery common outlet
17. Temperature
probe
NTC
for free cooling water inlet circuit
18. Temperature
probe
NTC
for free cooling external air temperature
19. Temperature
probe
NTC
for dynamic setpoint external air / boiler / change over
20. Temperature
probe
NTC
for combined defrost circuit #1
21. Temperature
probe
NTC
for combined defrost circuit #2
22. Temperature
probe
NTC
for auxiliary output #1
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...