1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Bottom display: circuit 2:
•
Evaporator 2 water outlet, with the label
OuT2.
Par.
dP03 = 2
Top display of the circuit 1:
•
Condenser 1 water inlet temperature with the label
CIn1
Bottom display of the circuit 1
•
Condenser 1water outlet with the label
COu1.
Top display of the circuit 2:
Condenser 2 water inlet temperature with the label
Cin2
Bottom display of the circuit 2
•
Condenser 2water outlet with the label
Cou2
.
Par.
dP03 = 3
Top display of the circuit 1:
•
Condenser probe temperature
Cdt1
/ pressure
CdP1
Bottom display of the circuit 1
•
Evaporator pressure probe
LP1
Top display of the circuit 2:
Condenser probe temperature
Cdt2
/ pressure
CdP2
Bottom display of the circuit 2
Evaporator pressure probe
LP2
15.4 D
EFAULT DISPLAY READ
-
OUT OF THE REMOTE PANELS
VI620S
AND
VI820S
If the parameter dP04 = 0 the upper display of the remote panels #1 and #2 depends on the parameter values dP01 – dP02 – dP03; to
show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm.
If the parameter dP04 = 1 the upper display of the remote panels #1 and #2 show their internal NTC sensor (ambient temperature); to
show the same temperature it is possible to eccess the function menu under the function trEm.
15.5 D
EFAULT DISPLAY READ
-
OUT OF THE REMOTE PANELS
VI620S
AND
VI820S
If the parameter dP04 = 0 the upper display of the remote panels #1 and #2 depends on the parameter values dP01 – dP02 – dP03; to
show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm.
If the parameter dP04 = 1 the upper display of the remote panels #1 and #2 show their internal NTC sensor (ambient temperature); to
show the same temperature it is possible to eccess the function menu under the function trEm.
16 DISPLAY INFORMATION
16.1 S
HOW THE
S
ET
P
OINT VALUE
Push and release the
SET
key, the leds of the circuits are off and the set value is displayed.
In stand-by the bottom display shows
SetC
(set chiller), by pushing SET again the next label is
SetH
(set heat pump ).
If the unit is running the only set displayed is related to the running mode.
16.2 M
ODIFY THE
S
ET
P
OINT
1) Push
SET
key for at least
3
seconds: the leds of the circuits are off and the set value is blinking.
2) Use
the
UP
or
DOWN
key to modify the setpoint.
3) Push
SET
to confirm or wait the timeout (15seconds).
16.3 S
HOW THE ACTIVE
S
ET
P
OINT DURING
E
NERGY
S
AVING OR
D
YNAMIC
S
ETPOINT
If the unit is running in chiller or HP, the Energy Saving or the Dinamic Setpoint activity is signalled by the blinking led of the SET button.
Chiller mode:
push
SET
one time, the bottom display shows the
SEtC
(set chiller) while the top display shows the set value. Only if the
Energy saving or the Dynamic Setpoint are active, pushing another time the
SET
key, the bottom display shows
“SEtr”
(real setpoint),
and the top display shows the setpoint that the unit is really using for the thermoregulation.
Chiller mode:
push
SET
one time, the bottom display shows the
SEtH
(set Heat pump) while the top display shows the set value. Only
if the Energy saving or the Dynamic Setpoint are active, pushing another time the
SET
key, the bottom display shows
“SEtr”
(real
setpoint), and the top diplay shows the setpoint that the unit is really using for the thermoregulation.
ATTENTION
The
SEtr
label appears only if the Energy saving or the Dynamic Setpoint are active.
To modify the working setpoint it is necessary the setpoint values is displayed on both the display (temperature / temperature or
temperature / pressure o pressure/ pressure) without any identification label, otherwise the SET key swaps to the circuit information.
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...