1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
22.2 G
RAPH OF THE COMPRESSOR THERMOREGULATION
I
N HEAT PUMP
22.3 GRAPH NEUTRAL ZONE COMPRESSOR CONTROL
Not yet available on this version
Compressor regulation in chiller
Compressor regulation in heat pump
22.4 GRAPH PROPORTIONAL INTEGRAL COMPRESSOR REGULATION CONTROL
Not yet available on this version
Compressor regulation in chiller
Compressor regulation in heat pump
23 THERMOREGULATION OF THE ANTI FREEZE, INTEGRATION HEATING OR
BOILER
23.1 T
HERMOREGULATION OF THE HEATERS IN CHILLER
The
Par. Ar06
selects the probe/s control for the anti-freeze alarm and the relay outputs configured as anti-freeze / support / boiler
heaters for the circuits 1 and 2 in chiller mode.
Par.
Ar06 = 0
: the function is disabled
Par.
Ar06 = 1
: the thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit 1 and 2 (or both together) is
controlled only throughout the NTC probe configured as evaporator water inlet.
Par.
Ar06 = 2
: the thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit #1 is controlled with NTC probe
configured as evaporator probe outlet of the circuit #1.
The thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit #2 is controlled with NTC probe configured as
evaporator probe outlet of the circuit #2.
ATTENTION:
It is not possible to control the heaters of the crcuit #1 with the probe of the circuit #2 and viceversa.
Par.
Ar06 = 3
: the thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit 1 and 2 (or both together) is
controlled throughout the NTC probe configured as evaporator water outlet circuit #1 or circuit #2 or evaporator water common outlet, or
if they are all configured, by the first probe that goes below the setpoint.
23.2 T
HERMOREGULATION OF THE HEATERS IN HEAT PUMP
The
Par. Ar07
selects the probe/s control for the anti-freeze alarm and the relay outputs configured as anti-freeze / support / boiler
heaters for the circuits 1 and 2 in heat pump mode.
Par.
Ar07 = 0:
the function is disabled
Par.
Ar07 = 1:
the thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit 1 and 2 (or both together) is
controlled only throughout the NTC probe configured as evaporator water inlet.
Par.
Ar07 = 2
: the thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit #1 is controlled with NTC probe
configured as evaporator probe outlet of the circuit #1.
The thermoregulation, the anti-freeze alarm and the relay outputs for heaters circuit #2 is controlled with NTC probe configured as
evaporator probe outlet of the circuit #2.
ATTENTION:
It is not possible to control the heaters of the crcuit #1 with the probe of the circuit #2 and viceversa.
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...