1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
80/105
After the interval dF09 determined by the defrost request of one of the circuits the other 2
nd
circuits must wait also the time dF06 before
defrosting.
dF07
Compressor off time before the defrost (the led of the compressor is blinking)
After the dF09 delay and before activating the defrost, the compressors are stopped for the dF07 time.
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and when dF07 is completely
expired the compressors and the defrost can start.
This procedure does not respect the compressor on delay protection therefore the compressor is immediately turned off and then on. If
dF07 = 0 the compressor is not stopped and the 4-way valve is immediately turned.
dF08
Compressor off time after the defrost (the led of the compressor is blinking)
After the defrost cycle the compressors are stopped for the dF08 time.
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and to drain the external
exchange unit, when dF08 is completely expired the unit restart in heat pump mode.
This procedure does not respect the compressor on delay protection therefore the compressor is immediately turned off and then on. If
dF08 = 0 the compressor is not stopped and the 4-way valve is immediately turned.
DF09
Delay time to next defrost
It starts when the condensing/evaporating temperature/pressure probe value is lower than dF02 setpoint. This time is reloaded if the
power supply fails, after a defrost cycle or from a digital input request of defrost.
The time counting is interrupted if the compressor is turned off or if the temperature/pressure is higher then dF02.
dF10
Temperature setpoint to start a combined defrost of the circuit #1.
It allows to set a temperature value to determines the beginning of a combined defrost.
After the dF09 counting the NTC probe of the combined defrost of the circuit #1 is compared to the dF10 setpoint, if the value is lower
the defrost starts otherwise the unit runs in heat pump mode and when the temperature decreases under dF10 the defrost immediately
starts.
dF11
Temperature setpoint to end a combined defrost of the circuit #1.
It allows to set a temperature value to determine the end of a combined defrost.
When the NTC probe of the combined defrost of the circuit #1 becomes higher than dF10 setpoint the defrost cycle stops.
dF12
Temperature setpoint to start a combined defrost of the circuit #2.
It allows to set a temperature value to determine the beginning of a combined defrost.
After the dF09 counting the NTC probe of the combined defrost of the circuit #2 is compared to the dF12 setpoint, if the value is lower
the defrost starts otherwise the unit runs in heat pump mode and when the temperature decreases under dF12 the defrost immediately
starts.
dF13
Temperature setpoint to end a combined defrost of the circuit #2.
It allows to set a temperature value to determine the end of a combined defrost.
When the NTC probe of the combined defrost of the circuit #2 becomes higher than dF13 setpoint the defrost cycle stops.
dF14
All the resources on during the defrost of the circuit #1
0= Not enabled
1= Enabled
dF15
All the resources on during the defrost of the circuit #2
0= Not enabled
1= Enabled
dF16
Compressor step delay time in defrost.
dF17
Condensing fan control during defrost and dripping cycle
0= Not enabled
1 = Enabled in defrost
2= Enabled in defrost and in dripping time
If dF17 = 0: During the defrost the fan control is not active.
If dF17 = 1: when the condensing temperature/pressure value increases over dF18 the fans are turned on. the fan control is determined
by the same algorithm used in chiller mode.
If dF17 = 2: during the dripping time (dF08 <>0) the fan are turned on for the time duration set in dF08 .
dF18
Pressure / temperature setpoint to force the fans on during the defrost
When the temperature/pressure rises over this value the fan are turned on at the maximum speed.
dF19
Time delay before starting a forced defrost
It determines a delay time before starting the defrost cycle
dF20
Temperature / pressure setpoint to force a defrost
It determines a temperature/pressure setpoint under which the dF19 starts counting, when dF19 is expired if the temperature/pressure
is still lower than dF20 the defrost is immediately executed.
ATTENTION
If during the dF19 counting the temperature rises over df20+dF21(differential) the process is aborted and the dF19 time
reloaded.
dF21
Forced defrost differential
dF22
defrost mode for unit with two circuits
Operative mode:
0= Independent
1= The condition are satisfied in both circuits
2= At least one circuit has reached the start condition
dF23
It determines the end of the defrost for unit having two circuit and common condensing ventilation
Operative mode:
0= Independent
1= The end defrost condition are satisfied In both circuits
2= At least one circuit has reached the end defrost condition
dF24
Start / stop defrost probe
Start / stop defrost from analog input
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur / pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator pressure probe
3= start and stop with evaporator pressure probe
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...