1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Sd 3
External air setpoint in chiller mode
-30.0
-22
70.0
158
°C
°F
Dec
int
Sd 4
External air setpoint in heat pump mode
-30
-22
70.0
158
°C
°F
Dec
int
Sd 5
External air differential in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 6
External air differential in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Energy saving
Parameters
Description
min
max
udm
Risoluzione
ES 1
Start of the Time band 1 (0÷24)
0
24.00
Hr
10 Min
ES 2
End of the Time Band 1 (0÷24)
0
24.00
Hr
10 Min
ES 3
Start of the Time band 2 (0÷24)
0
24.00
Hr
10 Min
ES 4
End of the Time Band 2 (0÷24)
0
24.00
Hr
10 Min
ES 5
Start of the Time band 3 (0÷24)
0
24.00
Hr
10 Min
ES 6
End of the Time Band 3 (0÷24)
0
24.00
Hr
10 Min
ES 7
Monday: energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 8
Tuesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 9
Wednesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 10
Thursday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 11
Friday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 12
Saturday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 13
Sunday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 14
Energy Saving setpoint offset in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 15
Energy Saving differential in chiller mode
0.0
0
25.0
45
°C
°F
Dec
int
ES 16
Energy Saving setpoint offset in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 17
Energy Saving differential in heat pump mode
0.0
0
25.0
45
°C
°F
Dec
int
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Compressors
Parameters Description
min
max udm
Risoluzione
CO 1
Minimum compressor ON time after the start-up.
0 250
10
sec
10 sec
CO 2
Minimum compressor OFF time after the switching off.
0 250
10
sec
10 sec
CO 3
ON delay time between two compressors or compressor and valve. During
this time the led of the next resource is blinking.
1 250 Sec
CO 4
OFF delay time between two compressors or compressor and valve. During
this time the led of the next resource is blinking.
0 250 Sec
CO 5
Output time delay after the main power supply start-up to the unit.
All the loads are delayed in case of frequently power failures.
0 250
10
Sec
10 sec
Partialization (Capacity Control)
CO 6
Functioning (see Capacity Control)
0= With on/off steps
1= Continuous with steps and direct action
2= Continuous with steps and reverse action
3= Continuous with steps and direct total action
0 3
CO 7
Start-up with minimum compressor power / automatic start-unloading valve
0 = Only at the compressor start-up (Minimum power automatic start-
unloading valve off)
1= At the compressor start-up and during the termoregulation (Minimum
power / automatic start-unloading valve off)
2 = Only at the screw compressor start-up (Minimum power automatic start-
unloading valve off)
3= At the compressor start-up and during the termoregulation (Minimum
power / Unloading valve ON with compressor off)
0 3
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...