1592015300 User manual iCHILL 200 L GB
r1.3 09/09/2005
Pg.
32/105
CF 71
Proportional output 2
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
CF 72
Proportional output 3
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
CF 73
Proportional output 4
0= Not enabled
1= Free cooling Dumper / Mixing valve
2= 3-way valve for hot water
3= Dumper for air change
4= auxiliary output
Relay driver ON / OFF
0
o 1
4
c28
Terminale remoto
CF 74
Remote Panel 1 configuration
0= Not enabled
1= with NTC ambient temperature sensor
2= without NTC ambient temperature sensor
0 2
CF 75
Remote Panel 2 configuration
0= Not enabled
1= with NTC ambient temperature sensor
2= without NTC ambient temperature sensor
0 2
CF 76
Offset of the NTC probe of the remote terminal # 1
-12.0
-10
12.0
53
°C
°F
Dec
int
CF 77
Offset of the NTC probe of the remote terminal # 2
-12.0
-10
12.0
53
°C
°F
Dec
int
Icon function
CF 78
Icon function
0=
chiller /
heat pump
1=
chiller /
heat pump
0 1
Chiller / heat pump selection mode
CF 79
0= from keyboard
1= from digital input
2= from analogue input
0 2
Automatic Change over
CF 80
Change over setpoint for chiller/ heat pump inversion if Par. CF80=2
-30.0
-22
70.0
158
°C
°F
Dec
int
CF 81
Change over temperature differential if Par. CF80=2
0
0
25.0
45
°C
°F
Dec
int
U. m. Unit of measurement
CF 82
°C or °F selection
0= °C / °BAR
1= °F / °psi
0 1
Voltage frequency
CF 83
Power supply frequency
0= 50 Hz
1= 60 Hz
2= cc voltage
( ATTENTION with Par. CF83 = 2 the proportional outputs for fan control are
not enabled and the frequency alarm is inhibited)
0 2
Serial Address
CF 84
Serial address
1
247
CF 85
Firmware Release
CF 86
Eeprom parameter map
Pr1
Password
0
999
Pr2
Password
0
999
Pr3
Password
0
999
Dynamic Setpoint
Parameters
Description
min
max
M. u. Resolution
Sd 1
Maximum dynamic Offset in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 2
Maximum dynamic Offset in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
Summary of Contents for ichill IC260L
Page 1: ...IC200L Series User manual dIXEL ...
Page 7: ......
Page 77: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 76 105 ...
Page 103: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 Pg 102 105 NOTE ...
Page 104: ...1592015300 User manual iCHILL 200 L GB r1 3 09 09 2005 ...