Hardware information
Rack mounting installation
Digi CM User Guide
186
Rack mounting installation
1
Attach enclosed bracket ears to rack as shown in illustration.
2
Follow safety precautions when placing the Digi CM unit on the rack.
Rack mounting safety precautions
▪
Distribute weight evenly in the rack to avoid overloading.
▪
Ensure proper ventilation with at least 12 inches (30 centimeters) of clearance on all sides.
▪
Check equipment nameplate ratings before connecting to the supply circuit to avoid overloads
that may damage over-current protection devices and supply wiring.
▪
Maintain reliable earthing for rack-mounting equipment, especially for supply connections.
▪
Install equipment in Restricted Access Areas only (dedicated equipment rooms/closets) in
accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA
70.
▪
Connect equipment to a DC supply source (reliably earthed) that is electrically isolated from the
AC source.
▪
Directly connect the equipment chassis to the DC supply system-grounding electrode conductor
or a bonding jumper from a grounding terminal bar (or bus) that is connected to the DC supply
system grounding electrode conductor.
▪
Contain equipment that has a connection between the grounded conductor of the same DC
supply circuit, the grounding conductor, and also the point of grounding of the DC system in the
same immediate area. Do not ground the equipment elsewhere.
▪
Locate the DC supply source within the same premises as the equipment.
▪
Route away and secure all DC input wiring from sharp edges to prevent chaffing as well as
provide strain relief.
▪
Provide a readily accessible disconnect device and protective device a fixed wiring for a DC
power supply suitable for the specified rated voltage and current. Disconnect and protective
devices to be rated 2A Amps maximum.
Rack shown in illustration is
not included with the Digi CM
unit.
Summary of Contents for Digi CM 16
Page 1: ...User Guide Digi CM 8 port 16 port 32 port and 48 port...
Page 63: ...Digi CM User Guide 63 User administration Administer users 64...
Page 130: ...Power Controller Cascade multiple Digi RPM units Digi CM User Guide 130...
Page 131: ...Digi CM User Guide 131 Port clustering Introduction 132 Configure port clustering 132...