Chapter 12 Descriptions of Parameter Settings | IED-S
12-03-14
the fault code F150 (Unqualified braking force test) occurs when changing the inspection
switch to automatic mode, and the elevator does not run.
Automatic braking force test once per day
1. Set the time (seconds) to run the braking force test in Pr.03-60 (Brake Test Duration),
ranging from 0.0 to 20.0 seconds. If Pr.03-60=0, the automatic test for braking force once
per day does not run.
2. Set the output torque to run the braking force test in Pr.03-61 (Brake Test Output Torque),
ranging from 0% to 200%.
3. Set the car moving distance during braking force test in Pr.03-62 (Brake Test Moving
Distance), ranging from 0.0 to 50.0 mm
4. Set Pr.03-63 (Brake Test Running Direction). If Pr.03-63=1, the elevator runs upward during
braking force test. If Pr.03-63=0, the elevator runs downward during braking force test.
5. Set the time to run the automatic braking force test once per day in Pr.03-64 (Brake Test
Time (Hour)) and Pr.03-65 (Brake Test Time (Minute)).
6. Set the physical floor to run the automatic braking force test in Pr.03-66 (Brake Test Floor),
ranging from 0 to 64 floors.
7. After finishing the setting, the elevator automatically runs to the designated floor (the
warning code 1116 (Recall, Braking force test) occurs) in the specified time every day while
idling (if the warning code 1115 (Wait, Braking force test) occurs during the elevator’s
running) to run the upward or downward braking force test (the warning code 1109 (Braking
force, Under test) occurs) with the brake OFF. In the process of test, car call cannot register
any call; hall call can register but not respond to the calls.
8. If the test result is qualified, the elevator returns to normal mode and the warning code 1112
(Braking force, Test, Qualified) occurs. But if the car moving distance is not smaller than
Pr.03-62 (Brake Test Moving Distance), the elevator malfunctions and is unavailable, and
the fault code F150 (Unqualified braking force test) occurs. At this time, change to the
manual mode first, and then press the external reset device, or press the RESET key on the
digital keypad, or press and hold both the upward operation and downward operation
buttons simultaneously for more than five seconds to reset the fault code F150. Moreover,
use the methods described in the “Manual braking force test” section above until the warning
code 1112 (Braking force, Test, Qualified) appears to make the elevator run automatically.
Otherwise, the fault code F150 (Unqualified braking force test) remains when changing from
manual to automatic mode, and the elevator does not run.
First Main Group Control
Second Main Group Control
Third Main Group Control
Fourth Main Group Control
Fifth Main Group Control
Sixth Main Group Control
Seventh Main Group Control
Default:
0
Settings 0–63S
Dispersed Waiting
Default:
0
Settings 0–65535 sec.
Sets the idle time that elevator automatically runs dispersed waiting.
Goal: To make elevator arrive within ten seconds when there is hall call from any floor in off-peak
hours
Method:
1. In parallel control, when normally there are at least two running elevators and Pr.03-75 is not
set to 0, you can execute dispersed waiting.
2. After elevator finishes responding to all car/hall calls in group control operation, time starts to
Summary of Contents for IED-S Series
Page 3: ......
Page 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Page 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Page 32: ...Chapter 3 Wiring IED S 3 7...
Page 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Page 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Page 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Page 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Page 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Page 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Page 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Page 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Page 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Page 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Page 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Page 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Page 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Page 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Page 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Page 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Page 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Page 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Page 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Page 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Page 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Page 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Page 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Page 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Page 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Page 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Page 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Page 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Page 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Page 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Page 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Page 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Page 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Page 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...