Chapter 12 Descriptions of Parameter Settings | IED-S
12-03-1
Chapter 12 Descriptions of Parameter Settings
03 Function Settings
: You can set this parameter during operation.
Hoistway Auto-tuning
Default:
0
Settings 0–1
When using the hoistway auto-tuning function, you must set IED-S to the inspection mode first
(manually) and set Pr.03-00=1. Then, change the elevator to automatic control, and the hoistway
auto-tuning function is enabled. The elevator runs downward to the lower limit first, and then runs
upward and searches the leveling signals and forced deceleration switch signals for each floor
for adjustment, and stops until it reaches the upper limit. Finally, it runs to the highest floor to stop.
Then, the hoistway auto-tuning is finished.
During hoistway auto-tuning, the displayed value for Pr.03-00 is 1. It automatically clears to 0
until the auto-tuning process is finished.
NOTE: If you stop the auto-tuning process by setting Pr.03-00 to 0, the auto-tuning process stops
but the elevator cannot run normally. You must finish the tuning process once it starts.
Sets the running speed during hoistway tuning (Pr.04-03 Hoistway Auto-tuning Speed). The
slower the speed, the accurate the tuning. The suggested speed is 0.25 m/s.
If the fault code F141 occurs during the hoistway auto-tuning, increase the setting time for
Pr.03-24. After the hoistway turning is finished, change Pr.03-24 to normal settings values.
Highest Physical Floor
Lowest Physical Floor
Default:
1
Settings 1–64F
If the actual floor is from B1F to 10F, then the lowest physical floor is 1; the highest physical floor
is 11.
When using group controls, set the physical floor based on the highest and lowest physical floors.
Example:
If the actual floor for Elevator 1 is B1F–9F,
If the actual floor for Elevator 2 is 1F–10F,
Single
Control
Elevator/Physical Floor
Lowest Physical Floor
Highest Physical Floor
Elevator 1
1
10
Elevator 2
1
10
Group
Control
Elevator/Physical Floor
Lowest Physical Floor
Highest Physical Floor
Elevator 1
1
10
Elevator 2
2
11
Group Control Station Number
Default:
0
Settings 0–7
You can only use one group control station number at one time among all group control
elevators.
Group Control Enabled
Default:
0
Settings 0–1
0: Single control operation
1: Group control operation
Summary of Contents for IED-S Series
Page 3: ......
Page 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Page 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Page 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Page 32: ...Chapter 3 Wiring IED S 3 7...
Page 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Page 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Page 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Page 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Page 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Page 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Page 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Page 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Page 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Page 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Page 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Page 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Page 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Page 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Page 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Page 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Page 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Page 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Page 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Page 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Page 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Page 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Page 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Page 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Page 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Page 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Page 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Page 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Page 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Page 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Page 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Page 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Page 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Page 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...