Troubleshooting
ASDA-B3
13-48
13
AL303 CANopen synchronization signal timeout
Trigger condition
and cause
Condition: the synchronization with the controller fails when you use the CANopen
IP mode (in B mode).
Cause: timeout of CANopen synchronization signal.
Checking method
and corrective action
1.
Make sure the communication between the servo drive and controller is good.
2.
Make sure the setting of synchronization cycle (0x1006) is identical to that of
the controller.
3.
Modify the synchronization error range setting (P3.009.U).
4.
Ensure the correct time sequence of sending packets from the controller.
A drift or delay in packet sending time causes synchronization failure.
5.
When the servo drive is in the operation mode of PV (Profile velocity mode) or
HM (Homing mode), check if P3.017 is set too low.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL305
SYNC period error
Trigger condition
and cause
Condition: CANopen 301 Obj 0x1006 Data Error.
Cause: SYNC period is in error.
Checking method
and corrective action
Check the value of 0x1006. If it is smaller than or equal to 0, this alarm occurs.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL304 Invalid interpolation mode command
Trigger condition
and cause
Condition: the servo drive cannot send the command when in CANopen IP mode
(except in B mode).
Cause: the interpolation command fails.
Checking method
and corrective action
The computing time takes too long. Disable the USB monitoring function.
How to clear the
alarm?
NMT: reset node or 0x6040 fault reset.
AL35F Emergency stop during deceleration
Trigger condition
and cause
The rising edge of DI(0x47) is triggered, and then the motor decelerates to 0 and
triggers AL3CF.
Checking method
and corrective action
Check if any of the parameters, P2.010 - P2.017 and P2.036 - P2.040, is set to
DI(0x47) and is triggered.
How to clear the
alarm?
Cycle power on the servo drive.
Summary of Contents for ASDA-B3 Series
Page 15: ... This page is intentionally left blank ...
Page 53: ...Installation ASDA B3 2 24 2 This page is intentionally left blank ...
Page 137: ...Wiring ASDA B3 3 84 3 This page is intentionally left blank ...
Page 161: ...Test Operation and Panel Display ASDA B3 4 24 4 This page is intentionally left blank ...
Page 285: ...Motion Control ASDA B3 7 66 7 This page is intentionally left blank ...
Page 477: ...Parameters ASDA B3 8 192 8 This page is intentionally left blank ...
Page 515: ...Absolute System ASDA B3 10 22 10 This page is intentionally left blank ...
Page 747: ...Troubleshooting ASDA B3 13 54 13 This page is intentionally left blank ...
Page 809: ...Accessories ASDA B3 B 32 B This page is intentionally left blank ...
Page 813: ...Revision History ASDA B3 4 This page is intentionally left blank ...