ASDA-A User Manual
Chapter 7 Parameters
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
4th Edition 2005/11/30,
HE03
7-31
P1 - 23
PO5H
5th Position Command for Rotation
Communication Addr.: 0117H
Default: 0
Applicable Control Mode: Pr
Range: +/-30000
This parameter is used to set rotation pulse number of internal position 5.
P1 - 24
PO5L
5th Position Command for Pulse
Communication Addr.: 0118H
Default: 0
Applicable Control Mode: Pr
Range: +/-max. cnt/rev
This parameter is used to set rotation cycle number of internal position 5.
Stroke5 = PO5H × (cnt/rev) + PO5L
P1 - 25
PO6H
6th Position Command for Rotation
Communication Addr.: 0119H
Default: 0
Applicable Control Mode: Pr
Range: +/-30000
This parameter is used to set rotation pulse number of internal position 6.
P1 - 26
PO6L
6th Position Command for Pulse
Communication Addr.: 011AH
Default: 0
Applicable Control Mode: Pr
Range: +/-max. cnt/rev
This parameter is used to set rotation cycle number of internal position 6.
Stroke6 = PO6H × (cnt/rev) + PO6L
P1 - 27
PO7H
7th Position Command for Rotation
Communication Addr.: 011BH
Default: 0
Applicable Control Mode: Pr
Range: +/-30000
This parameter is used to set rotation cycle number of internal position 7.
P1 - 28
PO7L
7th Position Command for Pulse
Communication Addr.: 011CH
Default: 0
Applicable Control Mode: Pr
Range: +/-max. cnt/rev
This parameter is used to set rotation pulse number of internal position 7.
Stroke7 = PO7H × (cnt/rev) + PO7L
P1 - 29
PO8H
8th Position Command for Rotation
Communication Addr.: 011DH
Default: 0
Applicable Control Mode: Pr
Range: +/-30000
This parameter is used to set rotation cycle number of internal position 8.