D-500 MK2 User Manual Firmware V-6.3
- 178 -
The controller is able to manage the supply of up to 5 prioritized loads. The loads are supplied starting
from the number #1 (highest priority) and unloaded from the highest number (lowest priority) available.
Protection timers help to stabilizing the decision algorithm and preventing unwanted multiple operations.
When the load is below the
Multi Load Add Power Level
during
Multi Load Add Start Delay
, then 1
step of load is added. The minimum wait period between two load_adds is
Multi Load Add Wait Delay
.
When the load is above the
Multi Load Substract Power Level
during
Multi Load Substract Start
Delay
, then 1 step of load is unloaded. The minimum wait period between two load_substracts is
Multi
Load Subtract Wait Delay
.
Add and subtract outputs send pulses of 0.25s duration.
The parameters used in Load Shedding feature are in the Electrical Parameters Group:
Multi Load Substract Power Level:
When the genset active power goes over this limit, the controller will
start subtracting load.
Multi Load Add Power Level:
When the genset active power goes below this limit, the controller will
start adding load.
Multi Load Substract Start Delay (
t
LSD
):
If the load stays over the
Multi Load Substract Power Level
parameter during this timer, then 1 step of load is substracted.
Multi Load Substract Wait Delay (
t
LSW
):
This is the minimum period between two load subtract pulses.
Multi Load Add Start Delay (
t
LAD
):
If the load stays below the
Multi Load Add Power Level
parameter
during this timer, then 1 step of load is added.
Multi Load Add Wait Delay (
t
LAW
):
This is the minimum period between two load add pulses.
t
1
:
the load goes below the Multi Load Add Power Level.
t
2
:
after Multi Load Add Start Delay the load is still below Multi Load Add Power Level, the Load_Add_1
sends a pulse.
t
3
:
after Multi Load Add Start Delay and Multi Load Add Wait Delay, the load is still below Multi Load Add
Power Level, thus Load_Add_2 output sends a pulse.
t
4
:
the load goes above the Multi Load Substract Power Level.
t
5
:
after Multi Load Substract Start Delay, the load is still above Multi Load Substract Power Level, thus the
Load_Substract_2 sends a pulse.
t
6
:
the load goes above the Multi Load Substract Power Level.
t
7
:
Multi Load Subtract Wait Delay is already expired. After Multi Load Subtract Start Delay, the load is still
above Multi Load Substract Power Level, thus the Load_Subtract_1 output sends a pulse.
34.3. FIVE STEP LOAD MANAGEMENT
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...