D-500 MK2 User Manual Firmware V-6.3
- 151 -
The unit is able to control motorized potentiometers through up/down output functions.
In order to use up/down functions, corresponding digital output function parameter should be set properly.
External potentiometers should be set to mid-point position at initial conditions.
If speed up/down outputs are enabled, the master unit will operate in order to adjust itself to the nominal
speed defined in program parameter
Nominal Frequency
.
If speed-up or speed-down functions are assigned to digital outputs, then the unit will start to generate speed
up/down pulses in order to control the external speed potentiometer. The analog GOV control output will be
still valid and functional.
The minimum speed pulse width is set through program parameter
Speed Up/Down Pulse Minimum
.
The minimum delay between two successive pulses is set through program parameter
Speed Up/Down
Pulse Delay
and the maximum speed pulse width is set through program parameter
Speed Up/Down
Pulse Maximum Duration
.
Parameter Definition
Description
Speed Up/Down
Pulse Minimum
Minimum pulse width in speed pulse control mode.
Speed Up/Down
Pulse Maximum Duration
Maximum pulse width in speed pulse control mode. If this parameter is
set to zero then no maximum pulse width is used.
Speed Up/Down
Pulse Delay
Minimum pulse delay between two speed up/down control pulses.
If voltage up/down outputs are enabled, the master unit will operate in order to adjust itself to the nominal
voltage defined in program parameter
Nominal Voltage
.
If voltage-up or voltage-down functions are assigned to digital outputs, then the unit will start to generate
voltage up/down pulses to control the external voltage potentiometer. The analog AVR control output will be
still valid and functional.
The minimum voltage pulse width is set through program parameter
Voltage Up/Down Pulse Minimum
.
The minimum delay between two successive pulses is set through program parameter
Voltage Up/Down
Pulse Delay
and the maximum voltage pulse width is set through program parameter
Voltage Up/Down
Pulse Maximum Duration.
Parameter Definition
Description
Voltage Up/Down
Pulse Minimum
Minimum pulse width in voltage pulse control mode.
Voltage Up/Down
Pulse Maximum Duration
Maximum pulse width in voltage pulse control mode. If this parameter is
set to zero then no maximum pulse width is used.
Voltage Up/Down
Pulse Delay
Minimum pulse delay between two of voltage up/down control pulses.
These outputs will be available in firmware version 5.7
25.2. VOLTAGE UP/DOWN CONTROL
25.1. SPEED UP/DOWN CONTROL
25. SPEED & VOLTAGE UP/DOWN RELAY OUTPUTS
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...