D-500 MK2 User Manual Firmware V-6.3
- 45 -
The synchronization functionality is used to parallel 2 or more gensets on the same busbar, in order to
increase the total genset power rating or in order to have redundancy/reserve power for a more reliable
operation.
A maximum of 48 gensets can be paralleled on the same busbar using D-500 units. Always one of the
gensets will become the MASTER one. It will determine the voltage and frequency of the busbar. When
more than one genset start together, the master genset will always feed the busbar first. Other gensets
will synchronize to the busbar, get in parallel and share the load.
When SYNCH mode is selected, the controller will monitor its REMOTE START input. If the remote start
input is active, it will run the genset (depending on settings). The remote start signal is usually provided
by a Mains Synchronization unit or an ATS controller. It can be a manually controlled signal as well.
If the Genset busbar is not energized, when the engine runs, the controller will immediately close the
genset contactor and feed the busbar. It will also become the MASTER.
If the genset Busbar is already energized, then the controller will synchronize the genset to the Busbar,
then close the genset contactor. After this, it will start to share the load.
Ramping for soft loading and unloading is provided as an inherent feature.
6.2 SYNCHRONIZATION FUNCTIONALITY
Max 48
gensets
Genset
Contactor
Genset
Busbar
Datalink
Bus
To mains
controllers
TO LOAD
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...