The unit offers full control for any brand and model of motorized circuit breakers (MCB).
The MCB control is performed through 3 digital output functions, namely Open, Close and Undervoltage
coil controls. Only 2 of these outputs are used in a single application.
Any digital output can be assigned to MCB control signals through programming menu.
The MCB CLOSE sequence is below:
Activate UV output, wait for undervoltage coil timer (t
uv
)
Activate CLOSE output, wait for close pulse timer (t
cl
)
Deactivate CLOSE output
The MCB OPEN sequence is below:
Deactivate UV output
Activate OPEN output, wait for open pulse timer (t
op
)
Deactivate OPEN output
If MCB feedback input is defined and the MCB fails to
change position after the expiration of MCB Fail timer,
then a fault condition will occur.
Open Pulse, Close Pulse and Undervoltage Coil timers
are adjusted through programming menu.
23. MOTORIZED CIRCUIT BREAKER CONTROL
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...