The D-500 includes a comprehensive set of protection functions to detect quickly a
mains failure
during
parallel with mains
operation.
The protections are enabled after the timeout defined by the parameter
Parallel Check Delay
in order not
to detect a mains failure during transients caused by the closing of the contactors.
If any of the protection functions detects a mains failure during parallel with mains:
-the mains contactor is immediately de-energized,
-a Parallel Mains Fail warning is generated,
-a specific warning to the related protection function is generated.
The ROCOF measures the frequency of the mains for each period. If the frequency change exceeds the
predefined limit for 4 successive periods, then the ROCOF function detects a mains failure. Thus the
response time of the ROCOF is approximately 4 cycles.
However the ROCOF will not detect relatively slow changes in mains frequency.
Related parameter:
ROCOF df/dt
If the parameter is set to zero, then the protection function will be disabled.
The Vector Shift measures and stores the period of last 5 cycles. At the end of each cycle it compares the
average period of last 2 cycles with the average period of 4
th
and 5
th
cycles. If the difference exceeds the
predefined limit, then the vector shift detects a mains failure. Thus the response time of the vector shift is
5 cycles.
However the vector shift will not detect relatively slow changes in mains frequency.
Related parameter:
Vector Shift Limit
If the parameter is set to zero, then the protection function will be disabled.
Immediate disconnection of the generator from the mains in
case of a mains failure, is required in most countries for
paralleling of synchronous generators to the mains.
32.2. VECTOR SHIFT FUNCTION
Do not forget that the protections are disabled during Parallel
Check Delay. Set this timeout as short as possible.
32.1. ROCOF FUNCTION (rate of change of frequency)
32. PROTECTION FUNCTIONS PARALLELING WITH MAINS
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...