D-500 MK2 User Manual Firmware V-6.3
- 103 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
Fuel Pulses per Volume
-
0
65000
1000
This is the number of pulses produced
by the flowmeter for the unit volume.
This parameter is characteristic of the
flowmeter used and should be set
according to the flowmeter data.
Fuel Counter Unit
-
Liter
Gallon
Liter
This is the unit for the fuel counter
SMS on Engine
Run/Stop
-
0
1
0
This parameter controls SMS sending
when the engine runs or stops. No
warnings generated.
0:
no SMS on engine run/stop
1:
SMS sent on engine run/stop
E-mail on Engine
Run/Stop
-
0
1
0
This parameter controls e-mail sending
when the engine runs or stops. No
warnings generated.
0: no e-mail on engine run/stop
1: e-mail sent on engine run/stop
Fuel Counter Type
-
0
1
0
This parameter determines the purpose
of fuel pulses
0: Fuel filling pulses, increment fuel
counter
1: Fuel consumption pulses, display
consumption.
Dual Genset Equal Aging
Enabled
-
0
1
0
0: Equal aging not enabled
1: Equal aging enabled
CT Secondary Rating
-
0
1
0
0: xxx/5A
1: xxx/1A
Automatic Topology
Detection
-
0
1
0
If this parameter is enabled, when the
engine runs, the controller will detect
the connection topology automatically
and will select alarm levels accordingly.
0: auto detect not enabled
1: auto detect enabled
Maintenance Done
Warning Enable
-
0
1
0
If enabled, the unit will generate a non-
visual warning when maintenance
counters are reset. In consequence,
SMS and e-mails will be sent, the
warning will be visible on the central
monitoring system.
0: maintenance warning disabled
1: maintenance warning enabled
Stop Status Screens
-
0
1
0
0: Enable status screens
1: Disable status screens
Time Zone
min
-720
+720
0
This parameter adjusts the time zone of
the controller, in order to allow internal
real time clock to be synchronized to
the UTC time.
GSM Location
Information
-
0
1
0
0:
no location information from GSM
1:
location information read from GSM
system.
Disable STOP at
Loaddump
-
0
1
0
0:
When Loaddump alarm occurs,
genset contactor opens and genset
runs until the end of the cooldown
1:
When Loaddump alarm occurs,
genset contactor opens but the genset
continues running without timeout.
17.1. CONTROLLER CONFIGURATION GROUP (continued)
Summary of Contents for D-500 MK2
Page 40: ...D 500 MK2 User Manual Firmware V 6 3 40 5 3 3 PHASE 3 WIRE DELTA 5 2 3 PHASE 4 WIRE STAR ...
Page 54: ...D 500 MK2 User Manual Firmware V 6 3 54 7 2 MAINS SYNCHRONIZATION FUNCTIONALITY ...
Page 55: ...D 500 MK2 User Manual Firmware V 6 3 55 7 3 SINGLE GENSET PARALLEL WITH MAINS FUNCT ...
Page 56: ...D 500 MK2 User Manual Firmware V 6 3 56 7 4 AMF FUNCTIONALITY ...
Page 57: ...D 500 MK2 User Manual Firmware V 6 3 57 7 5 ATS FUNCTIONALITY ...
Page 58: ...D 500 MK2 User Manual Firmware V 6 3 58 7 6 REMOTE START FUNCTIONALITY ...
Page 59: ...D 500 MK2 User Manual Firmware V 6 3 59 7 7 ENGINE CONTROL FUNCTIONALITY ...
Page 60: ...D 500 MK2 User Manual Firmware V 6 3 60 7 8 REMOTE DISPLAY PANEL FUNCTIONALITY ...